GFK-2306E A-1
Specifications
See page A-6 for a list of agency approvals for environmental service
and safety.
Physical
Enclosure dimensions
(actual – see ―Panel Cutout‖
in chapter 3 for cutout dimensions)
Height: 8.93 in (226.8 mm)
Width: 11.85 in (301.1 mm)
Height: 10.34 in (262.6 mm)
Width: 13.26 in. (336.8 mm)
DC Power
12 VDC (@ ±20% regulated power supply); or
24 VDC (@ ±20% regulated power supply)
-30% nominal input voltage, 10msec.
>200Mohm @ 1000V frame ground to 0V
>200Mohm @ 1000V frame ground to 24
Power Supply Conductor Size
12 to 18 AWG
For compliance to CE Mark, the isolated frame
ground must be connected.
Recommended frame ground connection is via the
shortest possible route, using 14 AWG.