Chapter 3: Configuration and commissioning 
Kilsen KFP-CF Series Installation Manual  41 
Expansion module output delay 
Use this menu to configure an expansion module output delay of up to 10 minutes, 
where the feature is available. 
To configure an expansion module output delay: 
1.  For output 1 on expansion module A, set the display as shown below, and then 
press Enter. 
 
The Expansion I/O Fault/Disabled LED on the control panel interface and the 
Activated LED on the expansion module flashes quickly to indicate that the 
module delay menu is active. 
2.  Select a value from 00 to 10 using the value selection buttons (2 and 4). 
3. Press Enter. 
4.  Repeat steps 1 to 3 as required for each output (1 to 4) on each installed module 
(A, B, C, and D) where a delay is required. 
5.  Save your changes.