Appendix A: Configuration presets 
Kilsen KFP-CF Series Installation Manual  61 
EN 54-2 Evacuation 
Configuration presets for EN 54-2 Evacuation are as follows. 
Two-zone control panels 
Code  Zone EOL  Sounder outputs  Zone type 
05 Passive  2  Mixed 
06 Passive, CleanMe 
enabled 
2 Mixed 
Note: CleanMe is not currently available for Kilsen detectors. 
 
Four- and eight-zone control panels 
Code  Zone EOL  Sounder outputs  Zone type 
05 Passive  4  Mixed 
06 Passive, CleanMe 
enabled 
4 Mixed 
 
Additional configuration characteristics are shown below. 
 
Default sounder delay  0 
Default zone delay  0n 
Start/Restart sounders  Start sounders or restart stopped sounders at access level 2 with or
without a fire alarm event 
 
Inputs and outputs are as follows. 
 
INPUT1 Remote reset 
INPUT2 Delays off 
OUT1 Sounder circuit 
OUT2 Sounder circuit 
OUT3 Sounder circuit 
OUT4 Sounder circuit 
Note: Two-zone control panels have only two outputs (OUT1 and OUT2).