EasyManuals Logo

GE L30 User Manual

GE L30
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #243 background imageLoading...
Page #243 background image
GE Multilin L30 Line Current Differential System 5-103
5 SETTINGS 5.4 SYSTEM SETUP
5
Figure 5–23: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2)
IEC 61850 functionality is permitted when the L30 is in “Programmed” mode and not in the local control mode.
USER 3 OFF/ON
To open BRK1-(Name)
D60, L60, and L90 devices from trip output
C60, D60, L60, and L90 relays from recloser
AND
AND
OR
AND
OR
OR
AND
AND
OR
AND
AND
AND
AND
AND
SETTING
= Enabled
BREAKER 1 FUNCTION
SETTING
Off = 0
BREAKER 1 BLOCK OPEN
FLEXLOGIC OPERANDS
TRIP PHASE A
TRIP PHASE B
TRIP PHASE C
TRIP 3-POLE
SETTING
Off = 0
BREAKER 1 OPEN
SETTING
= Enabled
BREAKER 1 PUSHBUTTON
CONTROL
USER 2 OFF/ON
To close BRK1-(Name)
SETTING
Off = 0
BREAKER 1 CLOSE
FLEXLOGIC OPERAND
AR CLOSE BKR 1
SETTING
Off = 0
BREAKER 1 BLOCK CLOSE
SETTING
MANUAL CLOSE RECAL1 TIME
0
FLEXLOGIC OPERAND
BREAKER 1 MNL CLS
FLEXLOGIC OPERAND
BREAKER 1 ON CMD
FLEXLOGIC OPERANDS
BREAKER 1 OFF CMD
BREAKER 1 TRIP A
BREAKER 1 TRIP B
BREAKER 1 TRIP C
To breaker control logic sheet 2
859711A2.CDR
BrkCSWI1.PosOpn.ctVal
BrkXCBR1.BlkOpn.ctlVal
AND
OR
OR
OR
OR
BrkXCBR1.BlkOpn.stVal
AND
AND
OR
0
20 ms
BrkCSWI1.PosCls.ctVal
AND
SETTING
Off = 0
XCBR1 ST.LOC OPERAND:
OR
AND
OR
BrkCBR1.BlkCls.ctVal
BrkXCBR1.BlkCls.stVal
61850 model
61850 model
61850 model
61850 XCBR config setting
61850 model
61850 model
61850 model
OR
BrkXCBR1.PosOpn.ctVal
BrkXCBR1.PosCls.ctVal
OR

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE L30 and is the answer not in the manual?

GE L30 Specifications

General IconGeneral
BrandGE
ModelL30
CategoryRelays
LanguageEnglish

Related product manuals