5-142 L30 Line Current Differential System GE Multilin
5.5 FLEXLOGIC 5 SETTINGS
5
ELEMENT:
Ground time
overcurrent
GROUND TOC1 PKP
GROUND TOC1 OP
GROUND TOC1 DPO
Ground time overcurrent 1 has picked up
Ground time overcurrent 1 has operated
Ground time overcurrent 1 has dropped out
GROUND TOC2 Same set of operands as shown for GROUND TOC1
ELEMENT
Non-volatile latches
LATCH 1 ON
LATCH 1 OFF
Non-volatile latch 1 is ON (Logic = 1)
Non-volatile latch 1 is OFF (Logic = 0)
LATCH 2 to 16 Same set of operands as shown for LATCH 1
ELEMENT:
Negative-sequence
instantaneous
overcurrent
NEG SEQ IOC1 PKP
NEG SEQ IOC1 OP
NEG SEQ IOC1 DPO
Negative-sequence instantaneous overcurrent 1 has picked up
Negative-sequence instantaneous overcurrent 1 has operated
Negative-sequence instantaneous overcurrent 1 has dropped out
NEG SEQ IOC2 Same set of operands as shown for NEG SEQ IOC1
ELEMENT:
Negative-sequence
overvoltage
NEG SEQ OV1 PKP
NEG SEQ OV1 DPO
NEG SEQ OV1 OP
Negative-sequence overvoltage element has picked up
Negative-sequence overvoltage element has dropped out
Negative-sequence overvoltage element has operated
NEG SEQ OV2 to 3 Same set of operands as shown for NEG SEQ OV1
ELEMENT:
Negative-sequence
time overcurrent
NEG SEQ TOC1 PKP
NEG SEQ TOC1 OP
NEG SEQ TOC1 DPO
Negative-sequence time overcurrent 1 has picked up
Negative-sequence time overcurrent 1 has operated
Negative-sequence time overcurrent 1 has dropped out
NEG SEQ TOC2 Same set of operands as shown for NEG SEQ TOC1
ELEMENT:
Neutral
instantaneous
overcurrent
NEUTRAL IOC1 PKP
NEUTRAL IOC1 OP
NEUTRAL IOC1 DPO
Neutral instantaneous overcurrent 1 has picked up
Neutral instantaneous overcurrent 1 has operated
Neutral instantaneous overcurrent 1 has dropped out
NEUTRAL IOC2 to 4 Same set of operands as shown for NEUTRAL IOC1
ELEMENT:
Neutral time
overcurrent
NEUTRAL TOC1 PKP
NEUTRAL TOC1 OP
NEUTRAL TOC1 DPO
Neutral time overcurrent 1 has picked up
Neutral time overcurrent 1 has operated
Neutral time overcurrent 1 has dropped out
NEUTRAL TOC2 Same set of operands as shown for NEUTRAL TOC1
ELEMENT:
Neutral directional
overcurrent
NTRL DIR OC1 FWD
NTRL DIR OC1 REV
Neutral directional overcurrent 1 forward has operated
Neutral directional overcurrent 1 reverse has operated
NTRL DIR OC2 Same set of operands as shown for NTRL DIR OC1
ELEMENT:
Synchrophasor
phasor data
concentrator
PDC NETWORK CNTRL 1
PDC NETWORK CNTRL 2
↓
PDC NETWORK CNTRL 16
Phasor data concentrator asserts control bit 1 as received via the network
Phasor data concentrator asserts control bit 2 as received via the network
↓
Phasor data concentrator asserts control bit 16 as received via the network
ELEMENT:
Phase directional
overcurrent
PH DIR1 BLK A
PH DIR1 BLK B
PH DIR1 BLK C
PH DIR1 BLK
Phase A directional 1 block
Phase B directional 1 block
Phase C directional 1 block
Phase directional 1 block
PH DIR2 Same set of operands as shown for PH DIR1
ELEMENT:
Phase
instantaneous
overcurrent
PHASE IOC1 PKP
PHASE IOC1 OP
PHASE IOC1 DPO
PHASE IOC1 PKP A
PHASE IOC1 PKP B
PHASE IOC1 PKP C
PHASE IOC1 OP A
PHASE IOC1 OP B
PHASE IOC1 OP C
PHASE IOC1 DPO A
PHASE IOC1 DPO B
PHASE IOC1 DPO C
At least one phase of phase instantaneous overcurrent 1 has picked up
At least one phase of phase instantaneous overcurrent 1 has operated
All phases of phase instantaneous overcurrent 1 have dropped out
Phase A of phase instantaneous overcurrent 1 has picked up
Phase B of phase instantaneous overcurrent 1 has picked up
Phase C of phase instantaneous overcurrent 1 has picked up
Phase A of phase instantaneous overcurrent 1 has operated
Phase B of phase instantaneous overcurrent 1 has operated
Phase C of phase instantaneous overcurrent 1 has operated
Phase A of phase instantaneous overcurrent 1 has dropped out
Phase B of phase instantaneous overcurrent 1 has dropped out
Phase C of phase instantaneous overcurrent 1 has dropped out
PHASE IOC2 to 4 Same set of operands as shown for PHASE IOC1
Table 5–17: L30 FLEXLOGIC OPERANDS (Sheet 3 of 7)
OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE L30 and is the answer not in the manual?

GE L30 Specifications

General IconGeneral
BrandGE
ModelL30
CategoryRelays
LanguageEnglish

Related product manuals