GE Multilin L30 Line Current Differential System 6-11
6 ACTUAL VALUES 6.2 STATUS
6
TOTAL RECEIVED PORT B is a counter for total messages received (either from DANPs or from SANs) on Port B.
TOTAL ERRORS is a counter for total messages received with an error (bad port code, frame length too short).
MISMATCHES PORT A is a counter for total messages received with an error on Port A (PRP frame, but port received through
and LAN ID in the frame do not match).
MISMATCHES PORT B is a counter for total messages received with an error on Port B (PRP frame, but port received through
and LAN ID in the frame do not match).