GE Multilin L30 Line Current Differential System B-17
APPENDIX B B.4 MEMORY MAPPING
B
Source Power (Read Only) (2 modules)
1C00 Source 1 Three Phase Real Power -1000000000000 to
1000000000000
W 0.001 F060 0
1C02 Source 1 Phase A Real Power -1000000000000 to
1000000000000
W 0.001 F060 0
1C04 Source 1 Phase B Real Power -1000000000000 to
1000000000000
W 0.001 F060 0
1C06 Source 1 Phase C Real Power -1000000000000 to
1000000000000
W 0.001 F060 0
1C08 Source 1 Three Phase Reactive Power -1000000000000 to
1000000000000
var 0.001 F060 0
1C0A Source 1 Phase A Reactive Power -1000000000000 to
1000000000000
var 0.001 F060 0
1C0C Source 1 Phase B Reactive Power -1000000000000 to
1000000000000
var 0.001 F060 0
1C0E Source 1 Phase C Reactive Power -1000000000000 to
1000000000000
var 0.001 F060 0
1C10 Source 1 Three Phase Apparent Power -1000000000000 to
1000000000000
VA 0.001 F060 0
1C12 Source 1 Phase A Apparent Power -1000000000000 to
1000000000000
VA 0.001 F060 0
1C14 Source 1 Phase B Apparent Power -1000000000000 to
1000000000000
VA 0.001 F060 0
1C16 Source 1 Phase C Apparent Power -1000000000000 to
1000000000000
VA 0.001 F060 0
1C18 Source 1 Three Phase Power Factor -0.999 to 1 --- 0.001 F013 0
1C19 Source 1 Phase A Power Factor -0.999 to 1 --- 0.001 F013 0
1C1A Source 1 Phase B Power Factor -0.999 to 1 --- 0.001 F013 0
1C1B Source 1 Phase C Power Factor -0.999 to 1 --- 0.001 F013 0
1C1C Reserved (4 items) --- --- --- F001 0
1C20 ...Repeated for Source 2
Source Frequency (Read Only) (2 modules)
1D80 Frequency for Source 1 2 to 90 Hz 0.001 F003 0
1D82 Frequency for Source 2 2 to 90 Hz 0.001 F003 0
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21E0 Breaker 1 Arcing Current Phase A 0 to 99999999 kA
2
-cyc 1 F060 0
21E2 Breaker 1 Arcing Current Phase B 0 to 99999999 kA
2
-cyc 1 F060 0
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21E4 Breaker 1 Arcing Current Phase C 0 to 99999999 kA
2
-cyc 1 F060 0
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21E6 Breaker 1 Operating Time Phase A 0 to 65535 ms 1 F001 0
21E7 Breaker 1 Operating Time Phase B 0 to 65535 ms 1 F001 0
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21E8 Breaker 1 Operating Time Phase C 0 to 65535 ms 1 F001 0
21E9 Breaker 1 Operating Time 0 to 65535 ms 1 F001 0
21EA ...Repeated for module number 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21EE ...Repeated for module number 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21F0 ...Repeated for module number 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21F2 ...Repeated for module number 2
Breaker Arcing Current Commands (Read/Write Command) (2 modules)
2224 Breaker 1 Arcing Current Clear Command 0 to 1 --- 1 F126 0 (No)
2225 Breaker 2 Arcing Current Clear Command 0 to 1 --- 1 F126 0 (No)
Passwords Unauthorized Access (Read/Write Command)
2230 Reset Unauthorized Access 0 to 1 --- 1 F126 0 (No)
Table B–10: MODBUS MEMORY MAP (Sheet 9 of 63)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT