EasyManuals Logo

GE L30 User Manual

GE L30
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #527 background imageLoading...
Page #527 background image
GE Multilin L30 Line Current Differential System B-17
APPENDIX B B.4 MEMORY MAPPING
B
Source Power (Read Only) (2 modules)
1C00 Source 1 Three Phase Real Power -1000000000000 to
1000000000000
W 0.001 F060 0
1C02 Source 1 Phase A Real Power -1000000000000 to
1000000000000
W 0.001 F060 0
1C04 Source 1 Phase B Real Power -1000000000000 to
1000000000000
W 0.001 F060 0
1C06 Source 1 Phase C Real Power -1000000000000 to
1000000000000
W 0.001 F060 0
1C08 Source 1 Three Phase Reactive Power -1000000000000 to
1000000000000
var 0.001 F060 0
1C0A Source 1 Phase A Reactive Power -1000000000000 to
1000000000000
var 0.001 F060 0
1C0C Source 1 Phase B Reactive Power -1000000000000 to
1000000000000
var 0.001 F060 0
1C0E Source 1 Phase C Reactive Power -1000000000000 to
1000000000000
var 0.001 F060 0
1C10 Source 1 Three Phase Apparent Power -1000000000000 to
1000000000000
VA 0.001 F060 0
1C12 Source 1 Phase A Apparent Power -1000000000000 to
1000000000000
VA 0.001 F060 0
1C14 Source 1 Phase B Apparent Power -1000000000000 to
1000000000000
VA 0.001 F060 0
1C16 Source 1 Phase C Apparent Power -1000000000000 to
1000000000000
VA 0.001 F060 0
1C18 Source 1 Three Phase Power Factor -0.999 to 1 --- 0.001 F013 0
1C19 Source 1 Phase A Power Factor -0.999 to 1 --- 0.001 F013 0
1C1A Source 1 Phase B Power Factor -0.999 to 1 --- 0.001 F013 0
1C1B Source 1 Phase C Power Factor -0.999 to 1 --- 0.001 F013 0
1C1C Reserved (4 items) --- --- --- F001 0
1C20 ...Repeated for Source 2
Source Frequency (Read Only) (2 modules)
1D80 Frequency for Source 1 2 to 90 Hz 0.001 F003 0
1D82 Frequency for Source 2 2 to 90 Hz 0.001 F003 0
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21E0 Breaker 1 Arcing Current Phase A 0 to 99999999 kA
2
-cyc 1 F060 0
21E2 Breaker 1 Arcing Current Phase B 0 to 99999999 kA
2
-cyc 1 F060 0
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21E4 Breaker 1 Arcing Current Phase C 0 to 99999999 kA
2
-cyc 1 F060 0
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21E6 Breaker 1 Operating Time Phase A 0 to 65535 ms 1 F001 0
21E7 Breaker 1 Operating Time Phase B 0 to 65535 ms 1 F001 0
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21E8 Breaker 1 Operating Time Phase C 0 to 65535 ms 1 F001 0
21E9 Breaker 1 Operating Time 0 to 65535 ms 1 F001 0
21EA ...Repeated for module number 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21EE ...Repeated for module number 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21F0 ...Repeated for module number 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21F2 ...Repeated for module number 2
Breaker Arcing Current Commands (Read/Write Command) (2 modules)
2224 Breaker 1 Arcing Current Clear Command 0 to 1 --- 1 F126 0 (No)
2225 Breaker 2 Arcing Current Clear Command 0 to 1 --- 1 F126 0 (No)
Passwords Unauthorized Access (Read/Write Command)
2230 Reset Unauthorized Access 0 to 1 --- 1 F126 0 (No)
Table B–10: MODBUS MEMORY MAP (Sheet 9 of 63)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE L30 and is the answer not in the manual?

GE L30 Specifications

General IconGeneral
BrandGE
ModelL30
CategoryRelays
LanguageEnglish

Related product manuals