GE Multilin L30 Line Current Differential System C-19
APPENDIX C C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
C
• Header.
• Substation.
• Communication.
• IED section (one or more).
• DataTypeTemplates.
The root file structure of an SCD file is illustrated below.
Figure C–6: SCD FILE STRUCTURE, SCL (ROOT) NODE
Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to
signals.
The Substation node describes the substation parameters:
Figure C–7: SCD FILE STRUCTURE, SUBSTATION NODE
842791A1.CDR
SCL
Header (id, version, revision, toolID, nameStructure)
IED Section (IED 2)
Communication
IED Section (IED 1)
Substation
Other IED Sections
DataTypeTemplates
842792A1.CDR
Substation
EquipmentContainer
VoltageLevel
Function
PowerSystemResource
Power Transformer
GeneralEquipment
EquipmentContainer
Bay
Voltage
PowerSystemResource
SubFunction
GeneralEquipment