2.2.1 Test
equipment
required
1 – Secondary injection test
equipment
capable of providing an ac voltage
supply of up to at least 120% of the relay setting.
1 – Multifinger test plug type MMLB 01 for use with test block type MMLG if fitted.
1 – Miniature split plug type MMLB 03 to fit relay plug bridge.
3 – Calibrated
multimeters
0–10 amp ac, 0–400 volt
ac.
1 – Set primary injection testing equipment.
2.2.2 General
If the relay is wired
through
an MMLG test block it is
recommended
that all
secondary injection tests should be carried out using this block.
Ensure that the main system current
transformers
are shorted before isolating the
relay from the current
transformers
in preparation for secondary injection tests.
DANGER:
DO NOT OPEN CIRCUIT THE SECONDARY CIRCUIT OF A CURRENT
TRANSFORMER SINCE THE HIGH VOLTAGE PRODUCED MAY BE LETHAL
AND COULD DAMAGE INSULATION.
When type MMLG test block facilities are installed, it is
important
that the sockets in
the type MMLB 01 test plug, which correspond to the current
transformer
secondary
windings, are LINKED BEFORE THE TEST PLUG IS INSERTED INTO THE TEST
BLOCK. Similarly, a MMLB 02 single finger test plug
must
be
terminated
with an
ammeter BEFORE IT IS INSERTED to
monitor
CT secondary currents.
It is assumed that the initial preliminary checks have been carried out.
2.2.3 Relay CT shorting switches
With the relay removed from its case, check electrically that the CT shorting switch
is closed.
2.2.4 Secondary injection testing
Connect the circuit as shown in Figure 1 and ensure that the current transformer
primary is open circuit and that if any earthing connections are fitted, they do not
short out the primaries of any current transformers.
Increase the voltage until the relay just operates.
Note the current in the relay (this can be done using the
miniature
split plug
inserted into the appropriate position of the plug bridge connected to an
ammeter).
It should be approximately 38mA at setting.
Note also the voltage at which the relay operates which should correspond to the
setting V
R
of the relay with a tolerance of ±10%. The total secondary current for
operation will be given on ammeter
A1. This test should be repeated for each pole
of the
relay.
Drop off/Pick up ratio.
Check that this ratio is greater than
50%.
13