1–10 MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
Physical specifications
DIMENSIONS
Size: ........................................................................... Base: 62 mm [2.44"] (W) × 90 mm [3.54"] (H) × 113 mm [4.45"]
(D) (+ terminals 10mm [0.39"])
Expansion: 62 mm [2.44"] (W) × 90 mm [3.54"] (H) × 113 mm
[4.45"] (D)
GCP: 153 mm [6.02"] (W) × 102 mm [4.02"] (H) × 35 mm [1.38"]
(D)
Weight (Base):.......................................................0.75 kg [1.65 lb]
Environmental specifications
APPROVALS
Applicable Council Directive According to
CE compliance: Low voltage directive EN60255-5, EN60947-1, EN60947-6-1
EMC Directive EN61000-6-2/ EN61000-6-4
ISO: Manufactured under a registered
quality program
ISO9001
ENVIRONMENTAL SPECIFICATIONS
Ambient temperatures:
Storage/shipping: - 40
o
C to 90
o
C *
Operating: -20
o
C to 60
o
C * (Base Unit and Basic Control Panel)
-20
o
C to 50
o
C * (Graphical Control Panel)
* 1" around Base Unit
Humidity: Operating up to 95% (non condensing) @ 55
o
C (As
per IEC60068-2-30 Variant 2, 6days)
Altitude: 2000 m (max)
Overvoltage Category: II
Ingress Protection: IP20 (Base Unit), IP54 (Control Panel)