EasyManua.ls Logo

GE NX-4-EUR

GE NX-4-EUR
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LOCATION 40 - SYSTEM TIMERS (14 segments, numerical data)
Location 40 contains the duration of various system timing functions. Example: If you want the
duration of the dynamic battery test to be 30 minutes, you should program [3]- [0]-[*] in
segment 1 of this location. The [3]-[0] is the number of minutes; the [*] stores the data, and
moves to the next segment of this location.
Segment 1
Dynamic battery test duration in minutes, 0-255 minutes (“0” = no test)
Segment 2
AC fail report delay in minutes, 0-255 minutes
Segment 3
Power up delay in seconds, 0-60 seconds (“0” = no power up delay)
Segment 4
Siren time in minutes, 1-255 minutes
Segment 5
Telephone line cut delay in seconds, 0-255 seconds (“0” = no telephone line
monitoring enabled)
Segment 6
Cross zone time in minutes, 0-255 (“0” = no cross zoning)
Segment 7
Chime time in 50 msec. (1/ 20th second) increments from 0-12 seconds (“0”
= follows zone 255 latched)
Segment 8
Dial delay in seconds, 0-255 seconds (0 no abort delay)
Segment 9
Fire alarm verification time in seconds, 120-255 seconds (“0” = no fire
alarm verification). Values less than 120 sec. are considered as 120 sec.
Segment 10
Listen-in time in seconds, 0-255 (“ 0” = no listen-in time)
Segment 11
Zone activity monitor feature timed in hours/days, 0-255 (“0” = disabled)
Segment 12
Auto arming warning timer, 1-255 minutes
Segment 13
Auto arming retry timer, 1-255 minutes
Segment 14
Programming Timeout, 1-255 minutes (“0” = 15 minutes)
LOCATION 41 - CODE REQUIREMENTS (1 segment, feature data)
Segment 1
1 = On: enables the 6-digit code option. If 6-digit option is enabled, all
arm/disarm codes and the “Go To Program Code” are 6 digits. If this
option is enabled, the default user 1 code is [1]-[2]-[3]-[4]-[5]-[6].
NOTE: IF YOU ENABLE THIS OPTION, VERIFY THAT THE “GO TO
PROGRAM CODE” IS A SIX-DIGIT CODE BEFORE YOU EXIT FROM
PROGRAMMING
2 = On: requires code entry for [*]-[9]-[8] (perform callback download) and
[*]-[9]-[9] (answer incoming call for download) functions
3 = On: enables Auto Cancel / Abort
4 = Reserved
5 = On: keypad shutdown mode
6 = On: user authorisation to enter program mode
7 = Reserved
8 = Reserved
LOCATION 42 - GO TO PROGRAM CODE (6 segments, numerical data)
Location 42 contains the “Go To Program Code”. This location contains a code with either 4 or
6 digits. If the 6-digit code option is enabled in Location 41, THIS CODE MUST CONTAIN SIX (6)
DIGITS. If this option is not enabled in location 41, the last 2 segments (digits) will be ignored.
With the NX-4 disarmed, the “Go To Program Code” can be used to enter the Program Mode.
NX-4-EUR Installation manual Page 51 02/07/06

Table of Contents

Related product manuals