Appendix B - Settings and Signals
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
Copy From 09 05 Group 1
Group 2
Group 3
Group 4
Allows displayed settings to be copied from a selected setting group
Copy To 09 06 No Operation
Group 1
Group 2
Group 3
Group 4
Allows displayed settings to be copied to a selected setting group
Setting Group 1 09 07 Enabled
Enabled
Settings Group 1. If the setting group is disabled from the configuration, then all associated settings and signals are hidden, with the
exception of this setting.
Setting Group 2 09 08 Disabled
Enabled
Settings Group 2. If the setting group is disabled from the configuration, then all associated settings and signals are hidden, with the
exception of this setting.
Setting Group 3 09 09 Disabled
Enabled
Settings Group 3. If the setting group is disabled from the configuration, then all associated settings and signals are hidden, with the
exception of this setting.
Setting Group 4 09 0A Disabled
Enabled
Settings Group 4. If the setting group is disabled from the configuration, then all associated settings and signals are hidden, with the
exception of this setting.
Tripping Mode 09 0E 3 Pole
1 and 3 Pole
Current Diff 09 0F Enabled
Enabled
To enable (activate) or disable (turn off) the Differential Protection: ANSI 87.
To get the differential protection fully active, it is necessary also to enable the differential protection in the group. Note that Phase Diff
setting and InterMiCOM64 Fiber setting are mutually exclusive as with Phase Diff enabled, the digital message exchanged has the structure
of the differential message (i.e. currents are sent to the remote end, etc) and with interMiCOM64 Fiber the digital message exchanged has
the structure and properties of the InterMiCOM64 Fiber.
Overcurrent 09 10 Disabled
Enabled
To enable (activate) or disable (turn off) the Phase Overcurrent Protection function. I> stages: ANSI 50/51/67
Neg Sequence O/C 09 11 Disabled
Enabled
To enable (activate) or disable (turn off) the Negative Sequence Overcurrent Protection function. I2> stages: ANSI 46/67
Broken Conductor 09 12 Disabled
Enabled
To enable (activate) or disable (turn off) the Broken Conductor function. I2/I1> stage: ANSI 46