SPS –48V Slimline Power Shelf
Models: J2007003L005 - alpha suffixes per Slimline Power System Brochure
Quick Start Guide
Information Alarm Connections
See the Slimline Power System Brochure for details.
Alarm connections are on the rear of the shelf – J1 is the Alarm Outputs and J2 is Alarm Inputs
Change alarm descriptions via LAN port (Web pages)
1. Only with 6 relay controller (..6R..).
2. Returns for R1 and R4 are bridged. Other returns are isolated.
Specifications and Application
• Specifications and ordering information are in the Slimline Power System Brochure available at www.gecriticalpower.com
• External Surge Protective Devices (SPDs) - are required on all AC inputs.
Equipment Safety is Approved in IEC 60664-1 Installation Category II environments.
• Equipment and subassembly ports: 1. are suitable for connection to intra-building or unexposed wiring or cabling;
2. can be connected to shielded intra-building cabling grounded at both ends.
• Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an Integrated Ground Plane
(Mesh-Bonding Network or Common Bonding Network).
• Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.
• Battery return may be either Isolated DC return (DC-I) or Common DC return (DC-C).
Reference Documents
These documents are available at www.gecriticalpower.com.
Document Title:
850035894 Galaxy Pulsar Edge Quick Start Guide
CC848836981 Pulsar Edge Controller Family Product Manual
Temperature:
North America – 50°C Max. with no derating. 2% / °C derating above 50°C to 75°C.
CE – 50°C Max.