B-54 T35 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
C8C0 ...Repeated for Direct Input 13
C8C4 ...Repeated for Direct Input 14
C8C8 ...Repeated for Direct Input 15
C8CC ...Repeated for Direct Input 16
C8D0 ...Repeated for Direct Input 17
C8D4 ...Repeated for Direct Input 18
C8D8 ...Repeated for Direct Input 19
C8DC ...Repeated for Direct Input 20
C8E0 ...Repeated for Direct Input 21
C8E4 ...Repeated for Direct Input 22
C8E8 ...Repeated for Direct Input 23
C8EC ...Repeated for Direct Input 24
C8F0 ...Repeated for Direct Input 25
C8F4 ...Repeated for Direct Input 26
C8F8 ...Repeated for Direct Input 27
C8FC ...Repeated for Direct Input 28
C900 ...Repeated for Direct Input 29
C904 ...Repeated for Direct Input 30
C908 ...Repeated for Direct Input 31
C90C ...Repeated for Direct Input 32
Direct Input/Output Alarms (Read/Write Setting)
CAD0 Direct Input/Output Channel 1 CRC Alarm Function 0 to 1 --- 1 F102 0 (Disabled)
CAD1 Direct Input/Output Channel 1 CRC Alarm Message Count 100 to 10000 --- 1 F001 600
CAD2 Direct Input/Output Channel 1 CRC Alarm Threshold 1 to 1000 --- 1 F001 10
CAD3 Direct Input/Output Channel 1 CRC Alarm Events 0 to 1 --- 1 F102 0 (Disabled)
CAD4 Reserved (4 items) 1 to 1000 --- 1 F001 10
CAD8 Direct Input/Output Channel 2 CRC Alarm Function 0 to 1 --- 1 F102 0 (Disabled)
CAD9 Direct Input/Output Channel 2 CRC Alarm Message Count 100 to 10000 --- 1 F001 600
CADA Direct Input/Output Channel 2 CRC Alarm Threshold 1 to 1000 --- 1 F001 10
CADB Direct Input/Output Channel 2 CRC Alarm Events 0 to 1 --- 1 F102 0 (Disabled)
CADC Reserved (4 items) 1 to 1000 --- 1 F001 10
CAE0 Direct Input/Output Ch 1 Unreturned Messages Alarm
Function
0 to 1 --- 1 F102 0 (Disabled)
CAE1 Direct Input/Output Ch 1 Unreturned Messages Alarm Msg
Count
100 to 10000 --- 1 F001 600
CAE2 Direct Input/Output Ch 1 Unreturned Messages Alarm
Threshold
1 to 1000 --- 1 F001 10
CAE3 Direct Input/Output Ch 1 Unreturned Messages Alarm
Events
0 to 1 --- 1 F102 0 (Disabled)
CAE4 Reserved (4 items) 1 to 1000 --- 1 F001 10
CAE8 Direct Input/Output Ch 2 Unreturned Messages Alarm
Function
0 to 1 --- 1 F102 0 (Disabled)
CAE9 Direct Input/Output Ch 2 Unreturned Messages Alarm Msg
Count
100 to 10000 --- 1 F001 600
CAEA Direct Input/Output Ch 2 Unreturned Messages Alarm
Threshold
1 to 1000 --- 1 F001 10
CAEB Direct Input/Output Channel 2 Unreturned Messages Alarm
Events
0 to 1 --- 1 F102 0 (Disabled)
CAEC Reserved (4 items) 1 to 1000 --- 1 F001 10
Remote Devices (Read/Write Setting) (16 modules)
CB00 Remote Device 1 GSSE/GOOSE Application ID (GOID) --- --- --- F209 “Remote Device
1“
CB21 Remote Device 1 GOOSE Ethernet APPID 0 to 16383 --- 1 F001 0
CB22 Remote Device 1 GOOSE Dataset 0 to 16 --- 1 F184 0 (Fixed)
CB23 Remote Device 1 in PMU Scheme 0 to 1 --- 1 F126 0 (No)
CB24 Reserved 0 to 3 --- 1 F626 0 (None)
CB25 ...Repeated for Device 2
Table B–10: MODBUS MEMORY MAP (Sheet 46 of 52)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT