UR Family Firmware 5.81 - Release Notes 9
versions can allow the reclose element to execute reclose shots. Changes to the autoreclose element
ensure that the element stays on “lockout” state when the described conditions are present.
GE tracking number: 581-4
P The “Non-Volatile Latches” elements have been changed to ensure they will maintain the output
status when cycling power to the relay
Products: B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35, T60
Corrected firmware: 5.81
Description: Changes to the Non-volatile Latches ensure that those elements maintain the output status
(on or off) when the relay is powered off and on. Previous firmware versions can allow the elements’
output to momentarily change state when the relay power cycles. Customers using the “non-Volatile
Latches” for protection or control purposes are advised to upgrade their relay firmware version.
GE tracking number: 581-5
Communications
C Changes to the GGIO4 data set prevent ”Data Access Errors” in its unbuffered report control block
Products: B30, B90, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T35, T60
Corrected firmware: 5.80
Description: GGIO_4 and GGIO_1 data sets have three report control blocks each. When at least four or
more data items are configured in GGIO_4 and eight or more within GGIO_1, firmware versions 5.71 and
5.80 can allow the GGIO_4 Un-buffered Report Control Block to show the following message “Data Access
Error: type-inconsistent”. The changes implemented to GGIO_4 with this release fix this communication
issue.
GE tracking number: 581-6

Table of Contents

Other manuals for GE UR series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE UR series and is the answer not in the manual?

GE UR series Specifications

General IconGeneral
TypeProtective Relay
SeriesUR (Universal Relay)
Frequency Range50/60 Hz
ManufacturerGE (General Electric)
Communication ProtocolsIEC 61850, DNP3, Modbus
MountingPanel
DisplayLCD display
Operating Temperature-40°C to +70°C
Protection FunctionsOvercurrent, differential, distance, frequency, voltage