(1) Motor inoperative
Is Power LED off ?
Is the circui
t breaker (MCCB)
switched ON?
Wiring short-circuit
Can not
Is the operation
switch on the RUN
position?
Motor over-load
Defective motor
Poor wiring
VAT20 malfunction
VAT20 malfunction
YES
Can you switch ON the
MCCB?
Power source
abnormality
Poor wiring
Place the operation
switch to
RUN
position.
Is the
T1-T2,T2-T3,T3-T1
output voltage in balance
condition?
ABNORMAL
NO
YES
YES (When the motor is not connected, and the voltoge differences between
wires are within +/- 3% can be treated as in balance condition.)
Normal
(within +/- 10% of nominal value)
NO
NO
Is the
voltage between
L1-L2 power input terminals
normal?
NO
Is there
any output voltage on
motor T1-T2-T3?
VAT20 malfunction