AF-70 LP User Guide
IP20 & IP66 (NEMA 4X)
AC Variable Speed Drive
0.37 – 22kW (0.5 – 30HP)
200 – 480V

Table of Contents

Questions and Answers

  • N
    norma73Sep 23, 2025
    What to do if GE AF-70 LP Inverter shows Internal memory fault (DSP)?
    • L
      lmorganSep 23, 2025
      Press the stop key. If the fault persists, consult you supplier.
  • H
    Hunter RobertsAug 23, 2025
    Why GE AF-70 LP Inverter shows Under voltage on DC bus?
    • V
      Valerie DuranAug 23, 2025
      An 'Under voltage on DC bus' error on your GE Inverter indicates that the incoming supply voltage is too low. This often occurs when power is removed from the drive. However, if it happens during operation, check the incoming power supply voltage and all components in the power feed line to the drive.
  • L
    laurasantiagoAug 25, 2025
    How to fix Power stage trip on GE Inverter?
    • J
      Joseph Smith Jr.Aug 25, 2025
      To address a power stage trip on the GE Inverter, check for short circuits on the motor and connection cable.
  • Z
    zsmithAug 26, 2025
    What causes Motor Thermal Overload (I2t) on GE AF-70 LP?
    • E
      elizabeth01Aug 26, 2025
      The GE Inverter trips with a 'Motor Thermal Overload (I2t)' when it has delivered >100% of the value set in F-08 for an extended period, preventing motor damage.
  • D
    David HodgesAug 27, 2025
    How to resolve Output Fault on GE AF-70 LP?
    • M
      Micheal FosterAug 27, 2025
      An Output Fault on the GE Inverter suggests a problem on the drive's output, such as a missing phase or imbalanced motor phase currents. Inspect the motor and its connections.
  • N
    nbaileySep 18, 2025
    What to do if GE Inverter shows Internal memory fault (IO)?
    • L
      Luke RogersSep 18, 2025
      Press the stop key. If the fault persists, consult you supplier.
  • A
    Antonio BurchSep 15, 2025
    What to do if GE Inverter is too cold?
    • H
      Heather JohnsonSep 15, 2025
      If the GE Inverter indicates an under temperature condition, the ambient temperature is less than -10°C. Raise the temperature above -10°C to start the drive.
  • C
    Christopher KimSep 16, 2025
    What to do if GE AF-70 LP displays Motor PTC thermistor trip?
    • M
      Marcus PerkinsSep 16, 2025
      If the GE Inverter indicates a Motor PTC thermistor trip, it means the connected motor thermistor has detected an over temperature condition. Check the wiring connections and the motor itself.
  • K
    Kathryn WilsonSep 6, 2025
    What to do if GE Inverter displays Modbus comms loss fault?
    • C
      Cameron MillerSep 7, 2025
      If the GE Inverter displays a Modbus comms loss fault, check the incoming Modbus RTU connection cable and ensure that at least one register is being polled cyclically within the timeout limit set in H-36 Index 3.
  • D
    Dawn HobbsSep 3, 2025
    What to check if GE Inverter shows DC bus ripple too high?
    • Q
      qyoungSep 4, 2025
      If the GE Inverter indicates that the DC bus ripple is too high, check that all incoming supply phases are present and balanced.