Questions and Answers

  • K
    Kathryn WilsonSep 6, 2025
    What to do if GE Inverter displays Modbus comms loss fault?
    • C
      Cameron MillerSep 7, 2025
      If the GE Inverter displays a Modbus comms loss fault, check the incoming Modbus RTU connection cable and ensure that at least one register is being polled cyclically within the timeout limit set in H-36 Index 3.
  • D
    David EvansAug 22, 2025
    What to do if GE Inverter is overheating?
    • G
      gillmichaelAug 22, 2025
      If the GE Inverter's heatsink is overheating, first, verify that the ambient temperature around the drive is within the specified limits. Ensure that cooling air can freely circulate around it. If necessary, improve panel ventilation. Make sure that the bottom entry and top exit vents are not obstructed.
  • D
    Dawn HobbsSep 3, 2025
    What to check if GE Inverter shows DC bus ripple too high?
    • Q
      qyoungSep 4, 2025
      If the GE Inverter indicates that the DC bus ripple is too high, check that all incoming supply phases are present and balanced.
  • J
    John JohnstonSep 2, 2025
    What to do if GE Inverter shows Brake channel over current?
    • S
      Samantha WatkinsSep 2, 2025
      If the GE Inverter reports a brake channel over current, check the external brake resistor condition and connection wiring.
  • D
    Dana TorresAug 31, 2025
    What should I do if my GE AF-70 LP Inverter shows an Input phase loss trip?
    • C
      Cindy MataSep 1, 2025
      If the GE Inverter displays an Input phase loss trip, verify that all incoming power supply phases are present and balanced.
  • T
    Terri VazquezAug 30, 2025
    How to fix Autotune Fault on GE Inverter?
    • F
      fsmithAug 30, 2025
      An Autotune Fault on the GE Inverter indicates that the motor parameters measured during autotune are incorrect. Check the motor cable and connections for continuity and ensure all three phases of the motor are present and balanced.
  • B
    Beth WatsonAug 29, 2025
    Why GE Inverter shows Over voltage on DC bus?
    • A
      Amanda WrightAug 29, 2025
      If the GE Inverter displays an 'Over voltage on DC bus' error, verify that the supply voltage is within the drive's allowed tolerance. If the fault occurs during deceleration or stopping, increase the deceleration time in F-04 or install a suitable brake resistor and activate the dynamic braking function with H-34.
  • D
    David HodgesAug 27, 2025
    How to resolve Output Fault on GE AF-70 LP?
    • M
      Micheal FosterAug 27, 2025
      An Output Fault on the GE Inverter suggests a problem on the drive's output, such as a missing phase or imbalanced motor phase currents. Inspect the motor and its connections.
  • Z
    zsmithAug 26, 2025
    What causes Motor Thermal Overload (I2t) on GE AF-70 LP?
    • E
      elizabeth01Aug 26, 2025
      The GE Inverter trips with a 'Motor Thermal Overload (I2t)' when it has delivered >100% of the value set in F-08 for an extended period, preventing motor damage.
  • L
    laurasantiagoAug 25, 2025
    How to fix Power stage trip on GE Inverter?
    • J
      Joseph Smith Jr.Aug 25, 2025
      To address a power stage trip on the GE Inverter, check for short circuits on the motor and connection cable.