Speedreferenceinput(Hz/RPM)
DisplayedinHzifF-10=0,otherwiseRPM
Drivedigitalinputstatus
DisplaysvalueoftheUserPIoutput
Appliedmotorvoltage(V)
ValueofRMSvoltageappliedtomotor
Heatsinktemperature(ᵒC)
TemperatureofheatsinkinᵒC
Runtimesincedateofmanuf.(Hours)
Notaffectedbyresettingfactorydefaultparameters
Runtimesincelasttrip(1)(Hours)
Run-timeclockstoppedbydrivedisable(ortrip),resetonnextenableonlyifatrip
occurred.Resetalsoonnextenableafteradrivepowerdown.
Runtimesincelasttrip(2)(Hours)
Run-timeclockstoppedbydrivedisable(ortrip),resetonnextenableonlyifatrip
occurred(under-voltsnotconsideredatrip)–notresetbypowerdown/powerup
cyclingunlessatripoccurredpriortopowerdown
Displaysmostrecent4tripswithtimestamp
Runtimesincelastdisable(Hours)
Run-timeclockstoppedondrivedisable,valueresetonnextenable
8mostrecentvaluespriortotrip,256mssampletime
Heatsinktemperaturelog(ᵒC)
8mostrecentvaluespriortotrip,30ssampletime
8mostrecentvaluespriortotrip,256mssampletime
8mostrecentvaluespriortotrip,22mssampletime
Internaldrivetemperaturelog(ᵒC)
8mostrecentvaluespriortotrip,30ssampletime
Internaldrivetemperature(ᵒC)
ActualinternalambienttemperatureinᵒC
CANopenprocessdatainput
Incomingprocessdata(RXPDO1)forCANopen:PI1,PI2,PI3,PI4
CANopenprocessdataoutput
outgoingprocessdata(TXPDO1)forCANopen:PO1,PO2,PO3,PO4
Accumulatedtimewithheatsink>85ᵒC
(Hours)
Totalaccumulatedhoursandminutesofoperationaboveheatsinktempof85ᵒC
Accumulatedtimewithdriveinternaltemp>
80ᵒC(Hours)
Totalaccumulatedhoursandminutesofoperationwithdriveinternalambientabove
80°C
Estimatedrotorspeed(Hz)
Invectorcontrolmodes,estimatedrotorspeedinHz
TotalnumberofkWh/MWhconsumedbythedrive.
Totalruntimeofdrivefans(Hours)
Timedisplayedinhh:mm:ss.Firstvaluedisplaystimeinhrs,pressuptodisplay
mm:ss.
Softwareversionandchecksum
Versionnumberandchecksum.“1”onLHsideindicatesI/Oprocessor,“2“indicates
powerstage
Driverating,drivetypeandsoftwareversioncodes
Uniquedriveserialnumber
Displaysthemagnetisingcurrent(Id)andtorquecurrent(Iq).PressUPtoshowIq
ActualPWMswitchingfrequency(kHz)
Actualswitchingfrequencyusedbydrive
Criticalfaultcounter–O-I
Theseparameterslogthenumberoftimesspecificfaultsorerrorsoccur,andare
usefulfordiagnosticpurposes.
Criticalfaultcounter–O-Volts
Criticalfaultcounter–U-Volts
Criticalfaultcounter–O-temp(h/sink)
Criticalfaultcounter–bO-I(chopper)
Criticalfaultcounter–O-hEAt(control)
Modbuscommserrorcounter
CANbuscommserrorcounter
I/Oprocessorcommserrors
PowerstageuCcommserrors
Drivepoweruptime(lifetime)(Hours)
Totallifetimeofdrivewithpowerapplied
PhaseUcurrentoffset&ref
PhaseVcurrentoffset&ref
PhaseWcurrentoffset&ref
Index1:Firemodetotalactivetime
Index2:FireModeActivationCount
TotalactivationtimeofFireMode
DisplaysthenumberoftimesFireModehasbeenactivated
Displayssignalsforfirstscopechannels1&2
Displayssignalsforfirstscopechannels3&4
Bootloaderandmotorcontrol