GFK-1504N Chapter 11 Analog Output Modules 11-7
IC200ALG320
Analog Output Module, 12 Bit Current, 4 Channels
Scaling
The following graph illustrates the relationship between the output data that is
provided to the module from the backplane, and the actual output current. The
range spans between 4mA and 20mA.
Count vs Output Current
0 3200 6400 9600 12800 16000 19200 22400 25600 28800 32000
Count
The following equation can be used to calculate specific output currents:
I
out
= 4mA + (count/32760) x 16.38mA
The count value must be a multiple of 8. If the module receives a count value
that is not a multiple of 8, it rounds the value down to the closest multiple of 8.
For example: