11-8 VersaMax Modules, Power Supplies and Carriers User's Manual GFK-1504N
11
IC200ALG320
Analog Output Module, 12 Bit Current, 4 Channels
Thermal Derating
The minimum recommended load resistance per channel depends on the
ambient temperature, the external voltage, and the orientation of the module
and DIN rail. The thermal derating is not affected by the type of carrier on which
the module is installed.
The total load requirement includes the impedance of the transducer being
driven. At higher ambient temperatures, it may be necessary to add resistance
in series with the load to reach the minimum load requirement.
A
A
B
A
B
B
Ambient Temperature
Minimum Load Resistance per Channel (Ohms)
60ºC
50ºC
55ºC
45ºC
40ºC
35ºC
30ºC
25ºC
20ºC
15ºC
10ºC
5ºC
1000
750
500
250
875
625
375
125
B
A
24VDC
B
A
24VDC
30VDC
30VDC