strona 12 INSTRUKCJA SERWISOWA GHC201.07 i GHC201.08
PPUH „GECO” Sp. z o.o. Wydanie I OD DNIA 2018-02-22
VII. PPROGRAMMING OF SYSTEM PARAMETERS
When the unit is switched on and correctness of its operation has been checked (factory settings are
standard settings) setting of system parameters of GHC201.08 begins.
In order to do that, the unit must be switched off with the button (three horizontal lines appear on the
screen). Then buttons and must be pressed and holded. When they are being pressed, the button
must be pressed too (short sound signal is activated). All three buttons must be pressed together for about
5 seconds. If any of the buttons is released at that time, programming will be interrupted. When this activity is
done, diode on button will flash and symbol ‘c2’ will appear on the display for 1 second. Then the latest
programmed value of the parameter will appear. Now, using buttons the new values should be set;
every longer pressing of the button will cause quick winding of possible settings. Then should be pressed to
accept the set data and start programming of a new parameter.
It is possible to change some settings only if you do not want to change a given parameter, press
and
GHC201.08 will move to the next parameter.
After entering the last parameter setting and accepting it with the button , it will automatically exit the
programming mode and return to STANDBY mode (two horizontal lines on the display).
If no button is pressed within 20 seconds, the device will exit the parameter programming mode.
Notice !!!
Incorrect set of parameters settings may cause a faulty operation!!!
Table 2: Significance of parameters
Para-
metr
Opis
Min
Max
Krok
Nastawa
fabryczna
c2
Minimal time of compressor stoppage
0
15
1min
3 min
c5
Maximal time of operation of compressor
0 no testing (this parameter is off)
0
99
1min
40 min
c6
Time of compressor stoppage after switching on of protection from
parameter ‘c5’
1
99
1min
10 min
c8
Compressor operation time / heater stoppage time if the control
sensor is damaged
1
99
1min
25 min
c9
Compressor stoppage time / heater operation time if the control
sensor is damaged
1
40
1min
5 min
d0
Minimal temperature for a client to set
-40
119
1°C
1 °C
d1
Maximal temperature for a client to set
d0+1
120
1°C
10 °C
d2
Heating hysteresis for block 1 or hysteresis when r5=2
1
10
1°C
2 °C
d3
Cooling hysteresis for block 1
1
10
1°C
2 °C