4-53
Actual Dec time =
Time of Decel 1 or 2 x Preset Frequency
Motor rated output frequency
V/F Maximum output frequency = parameter 01-02 when programmable V/F is selected by 01-
00=7.
Motor rated output frequency is set by parameter 02-06.
V/F Maximum output frequency = 50.00 hz or 60.00 hz when preset V/F patterns are selected.
01- 00≠7.
Examples is in V/F mode:
01-00 7, 01-02 =50Hz, 05-02=10Hz (preset speed 1),
05-19 = 5s (Accel time), 05-20=20s (Decel time)
(
  1   
)
=
(
05-19
)
×
(
10 [ Hz]
)
(
01-02
)
=
1 [s]
(
  1   
)
=
(
05-20
)
×
(
10 [ Hz]
)
(
01-02
)
=
4 [s]
Multi speed run/stop cycles with Individual Accel/Decel times. 05-00=
1
Two modes are shown below:
Mode1 = On/Off run command
Mode2= Continuous run command
Mode1 Example: 00- 02=1(External Run/Stop Control).
00- 04=1(Operation ModeRun/stop-forward/reverse).
S1: 03- 00=0(RUN/STOP );
S2: 03- 01=1(Forward/Reverse);
S3: 03- 02=2(Preset speed 1);
S4: 03- 03=3(Preset speed 2);
S5: 03- 04=4(Preset speed 4);
a b c d e f
RUN RUN RUN
ON
ON
STOP STOP STOP
OFF
OFF
RUN
command
S2
S3
S4
05-01
05-02
05-03
Preset
speed0
Preset
speed1
Preset
speed2
Hz
T
FWD
OFF
When the run command is On/Off, acceleration and deceleration times for each cycle can be
calculated as below: time unit is in seconds.