06- Auto Run(Auto Sequencer) function
06- 00
Auto Run( sequencer) mode selection
Range
0:Disabled
1
:Single cycle (Continues to run from the unfinished step if restarted).
2
:Periodic cycle. (Continues to run from the unfinished step if restarted).
3
:Single cycle, then holds the speed of final step to run.
(Continues to run from the unfinished step if restarted).
4
:Single cycle. (Starts a new cycle if restarted).
5
:Periodic cycle. (Starts a new cycle if restarted).
6
:Single cycle, then hold the speed of final step to run.
(Starts a new cycle if restarted).
Frequency of the step 0 is set by parameter 05-01 keypad Frequency.
06- 01
Auto _ Run Mode Frequency Command 1
06- 02
Auto _ Run Mode Frequency Command 2
06- 03
Auto _ Run Mode Frequency Command 3
06- 04
Auto _ Run Mode Frequency Command 4
06- 05
Auto _ Run Mode Frequency Command 5
06- 06
Auto _ Run Mode Frequency Command 6
06- 07
Auto _ Run Mode Frequency Command 7
Range
0.00 ~ 599.00Hz
06- 16
Auto_ Run Mode Running Time Setting0
06- 17
Auto_ Run Mode Running Time Setting1
06- 18
Auto_ Run Mode Running Time Setting2
06- 19
Auto_ Run Mode Running Time Setting3
06- 20
Auto_ Run Mode Running Time Setting4
06- 21
Auto_ Run Mode Running Time Setting5
06- 22
Auto_ Run Mode Running Time Setting6
06- 23
Auto_ Run Mode Running Time Setting7
Range
0.00 ~ 3600.0s
06- 32
Auto_ Run Mode Running Direction0
06- 33
Auto_ Run Mode Running Direction1
06- 34
Auto_ Run Mode Running Direction2
06- 35
Auto_ Run Mode Running Direction3
06- 36
Auto_ Run Mode Running Direction4
06- 37
Auto_ Run Mode Running Direction5
06- 38
Auto_ Run Mode Running Direction6
06- 39
Auto_ Run Mode Running Direction7
Range
0: STOP 1: Forward 2: Reverse
Auto Run sequencer mode has to be enabled by using one of the multifunctional inputs S1 to S5
and setting the relevant parameter 03-00 to 03-04 to selection18.
Various Auto Run (sequencer) modes can be selected by parameter (06-00) as listed above.
7 Auto Run (sequencer) modes can be selected by parameters (06-01~06-39)
Auto Run frequency commands1 to 7 are set with Parameters (06-01 ~ 06-07),
Sequence run times are set with parameters (06-17 ~ 06-23)
FWD/REV Direction for each sequence can be set with parameters (06-33 ~ 06-39).
Auto sequence 0, frequency is set from keypad by parameter 05-01, sequence run time and
direction are set by parameters 06-16 and 06-32.