2.3. DESCRIPTION OF POWER TERMINALS
2.4. DESCRIPTION OF CONTROL TERMINALS
Terminals
U, V, W
C
D
U3, V3
Function
Power supply via AC mains, 3Ph (400V –15% up to 480V +10%)
Positive terminal to be connected to the inverter DC-LINK
Negative terminal to be connected to the inverter DC-LINK
Supply for internal fan (only for 1050A size and higher) (1Ph, 230V ± 15%)
Terminals
23
32
33
34
35
36
37
52
70, 72
81, 82
Function
Input of the precharge enable control
Output of the MLP static signal (low - active signal)
(Common) Ground of the MLP and ML static signals
Reference point for Power supply +24V
Power supply output +24V
Output of the ML signal (low - active signal)
Power supply of the ML and MLP signals
(Common) Ground of the precharge enable control
OK Relay
Blown fuse.
On SM32-480-1050, 1500 and 2000A sizes only.
Voltage, Current
(15 - 35V, 5 - 11mA)
(5 … 35V, 20mA source)
-
-
(32V / 300mA max)
(5 … 35V, 20mA max sink)
(35V max)
-
(max. 250VAC, 1A - AC11)
(max. 250VAC, 1A - AC11)
Figure 2.4.1: Terminals location
a) = control terminals
b) = power terminals
c) = power terminals (U3, V3) and control terminals (81, 82)
185 ... 650 A sizes
a)
b)
1050 ... 1500 A sizes
a)
b)
c)