—————— INSTRUCTION MANUAL——————
NOTE!
The use of AC mains choke on the power supply input is MANDATORY
2.6. CONVERTER SIZE SELECTION
Within the specified voltage field, the SM-32 converter supplies the same rated direct
current independently of the voltage itself. The increase of the output voltage causes an
increasing in the transferred power, whereas inverters are devices with a typically constant
transferred power (the supplied current decreases with the increasing of the output voltage).
As for the choice, therefore, the calculation is based on a common unit, the direct current
of the intermediate circuit, which, as for the inverters, is not mentioned into the product
instruction manual and has therefore to be calculated. Furthermore, the confrontation
between the two foreseen functioning classes has to be homogeneous (IEC 146 class 1 and
2).
2.6.1. Output Rated Currents for the Two Functioning Classes
Converter
SM32-480-185
SM32-480-280
SM32-480-420
SM32-480-650
SM32-480-1050
SM32-480-1500
SM32-480-2000
Main
frequency
[Hz]
50/60
50/60
50/60
50/60
50/60
50/60
50/60
Rated inductance
[mH]
0.148
0.085
0.085
0.06
0.03
0.019
0.016
Main three-phase inductance
Rated AC
current [A]
173
297
297
550
869
1425
1712
Saturation
current [A]
350
600
600
1050
1303
2138
2568
Type
LR3 - 090
LR3 - 160
LR3 - 315
LR3 869-1303-0,03
LR3 1425-2138-0,019
LR3 1425-2138-0,019
LR3-1712-2568-0,016
2.5.4. AC Mains Choke
Converter
SM32-480-185
SM32-480-280
SM32-480-420
SM32-480-650
SM32-480-1050
SM32-480-1500
SM32-480-2000
IEC 146 Class 1 *
185 A
280 A
420 A
650 A
1050 A
1500 A
2000 A
IEC 146 Class 2 **
150 A
225 A
340 A
540 A
850 A
1300 A
1500 A
DC link current (Terminals C / D)
* Continuous service
** Service with overload possibility of 150% for 60 seconds