—————— INSTRUCTION MANUAL——————
The current value in column „Current Dclink I
DCL
Continuous class 1“ is calculated as:
I
DCL
= P
Mot
/ (
η
Mot
x
η
I
x U
LN
x 1.35)
where for column „Current Dclink I
DCL
Continuous class 2“ it is obtained multiplying by
1.36.