Menu levels Submenu Display Function Value range Default setting
ProcCtrlMode* Switch process controller
on or off
ON / OFF OFF
ProcCtrl* Submenu for setting process controller parameters
Proc-P KP amplification of the
process controller
0,0 ... 100,0 0,5
Proc-I Ti reset time for the
process controller
0.0 ... 999.9 s 2.0 s
Proc-D KD component of the
process controller
0,0 ... 100,0 0,0
Proc-T Process controller Tv
time
1 ... 10,000 ms 1000 ms
IxType Defines the type of
actual value filter
OFF / RC / avr OFF
IxTime Filter time for actual
value input
0.10 ... 20.00 s 0.10 s
PosCtrl Submenu for setting positioner parameters
Pos P P amplification of the po-
sitioner
0.0 ... 100,0** 1.0
Pos D D amplification of the po-
sitioner
0,0 ... 100,0 0.0
Pos T Decay time of the D com-
ponent of the positioner
1 ... 5000 ms 100 ms
MinPos Closing limit = lower pos-
ition of control range
0 ... 100 % 0.0 %
MaxPos Stroke limitation = upper
position of control range
0 ... 100 % 100 %
CloseTight Lower close tight func-
tion
0 ... 20 % 0 %
OpenTight Upper close tight func-
tion
80 ... 100 % 100 %
DeadBand Permissible system devi-
ation
0.1 ... 25 % 1.0%, K-no.
2442: 2.0%, K-
no. 2443: 5.0%
Digital input Submenu for setting the digital inputs
In W Determines the function
of the digital input "In W"
OFF / ON OFF
Safe / ON
ParmSetB0
ParmSetB1
Poti / Ix
In X Determines the function
of the digital input "In X"
OFF / ON OFF
Safe / ON
ParmSetB0
ParmSetB1
Poti / Ix
In 1 Determines the function
of the digital input "In 1"
OFF / ON OFF
Safe / ON
ParmSetB0
ParmSetB1
Poti / Ix