**Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters. Rating definitions - Standby: Applicable
for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). * Maximum
wattage and current are subject to and limited by such factors as fuel Btu/megajoule content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for
each 1,000 feet (304.8 meters) above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60°F).
Generator
Model 005888-0
Rated Maximum Continuous Power Capacity (LP) 7,000 Watts*
Rated Maximum Continuous Power Capacity (NG) 6,000 Watts*
Rated Voltage 240
Rated Maximum Continuous Load Current – 240 Volts 29.2 / 25
Main Line Circuit Breaker 30 Amp
Phase 1
Number of Rotor Poles 2
Rated AC Frequency 60Hz
Power Factor 1.0
Battery Requirement (not included) Group 26R, 12 Volts and 525 CCA Minimum
Unit Weight (Pounds/Kilos) 250/113.4
Dimensions (L x W x H) in./mm 24.4 x 30.2 x 33/618.5 x 767.5 x 837
Sound output in dB(A) at 23 ft. (7m) with generator operating at normal load** 67
Engine
Type of Engine GENERAC OHV
Number of Cylinders 1
Displacement 432cc
Cylinder Block Aluminum w/Cast Iron Sleeve
Valve Arrangement Overhead Valve
Ignition System Solid-state w/Magneto
Governor System Mechanical
Starter 12 VDC
Oil Capacity Including Filter Approx. 1.1 Qts./1.0L
Operating RPM 3,600
Fuel Consumption
Natural Gas ft³/hr (m³/hr)
1/2 Load
Full Load
Liquid Propane ft
3
/hr (gal/hr) [Liters/hr]
1/2 Load
Full Load
85 (2.41)
148 (4.19)
36 (0.99) [3.75]
46 (1.26) [4.79]
Note: Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet at all load ranges - 5-7" water column (9-13mm mercury) for natural gas, 10-12" water column (19-22mm
mercury) for LP gas.
For Btu content, multiply ft
3
/hr x 2500 (LP) or ft
3
/hr x 1000 (NG)
For Megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG)
Controls
Digital LED Indicators Simple user interface for ease of operation.
Mode Switch: Auto Automatic Start on Utility failure. 7 day exerciser.
Off Stops unit. Power is removed. Control and charger still operate.
Manual/Test (start) Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Engine Start Sequence Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration)
Engine Warm-up 5 sec.
Engine Cool-Down 1 min.
Starter Lock-out Starter cannot re-engage until 5 sec. after engine has stopped.
2.5 Amp Timed Trickle Battery Charger Standard
Automatic Voltage Regulator w/Overvoltage Protection Standard
Automatic Low Oil Pressure Shutdown Standard
Overspeed Shutdown Standard, 72Hz
High Temperature Shutdown Standard
Overcrank Protection Standard
Safety Fused Standard
ES Standby Generator System - 7 kW specifications
7kW