Owner’s Manual for Mobile Light Tower 27
Section 5: Troubleshooting
General Troubleshooting
Some of the more common problems are listed in the
table below. This information is intended to be a check or
verification that simple causes can be located and fixed.
It does not cover all types of problems. Refer to the OEM
engine operator’s manual for additional troubleshooting
information. Procedures that require in-depth knowledge
or skills should be referred to a GMASD.
If problems persist, contact Generac Mobile at 1-800-926-9768 for assistance.
(000139)
WARNING
Risk of burns. Allow engine to cool before
draining oil or coolant. Failure to do so could
result in death or serious injury.
General Troubleshooting Guide
Problem Possible Cause Solution
Low oil pressure
shutdown
Low oil level Verify oil level on dipstick. Add oil, if needed.
Oil leaking from engine Visually inspect the engine for leaks.
Oil pressure switch failure Refer to OEM engine operator’s manual to identify corrective action.
High coolant temperature
shutdown
Low coolant level
Add coolant if needed. Allow engine to cool, then check coolant level in
radiator. Restart engine and check coolant temperature. Stop engine
immediately if coolant temperature is 210°F (99°C) or more.
Blockage in radiator
Inspect radiator shroud and ducting for blockage and remove any foreign
matter.
Leakage in coolant hoses,
engine block, or water pump
Inspect for visible leaks. Verify tension of water pump serpentine drive
belt.
Remove load on generator and restart engine. Verify coolant
temperature and shut engine down immediately if it starts to overheat.
Refer to the OEM engine operator’s manual for additional information on
engine overheating.
Unit cranks, but will not
start
Fuel level low
Check fuel level in tank.
Verify fuel pump operation.
Restricted air filter
Inspect air filter for blockage.
Refer to OEM engine operator’s manual for additional information.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Generac Power Systems MLT3060MV and is the answer not in the manual?

Generac Power Systems MLT3060MV Specifications

General IconGeneral
BrandGenerac Power Systems
ModelMLT3060MV
CategoryLighting Equipment
LanguageEnglish

Related product manuals