12
A small current is introduced into the compressor from the terminal, so that the compressor
can achieve a preheating effect due to the heating of the coil when the compressor is not
rotating.
⚫ Sensor redundancy and automatic shutoff
If one temperature sensor malfunctions, the air conditioner continues operation and displays
the corresponding error code, allowing for emergency use.
When more than one temperature sensor is malfunctioning, the air conditioner ceases
operation.
⚫ Automatic shutoff based on indoor fan speed
If the indoor fan speed registers below 300RPM or over2000RPM for an extended period of time, the
unit stops operation and the corresponding error code is displayed on the indoor unit.
⚫ Indoor fan delayed operation
When the unit starts, the louver is automatically activated and the indoor fan will operate
after a period of setting time or the louver is in place.
If the unit is in heating mode, the indoor fan is regulated by the anti-cold wind function.
3.3 Basic functions
3.3.1Abbreviation
3.3.2 Ventilation mode
Compressor and outdoor unit fan motor stop to work.
Temperature can’t be set and room temperature is displayed.
Can set turbo/high/middle/low/auto fan speed.
The louver operation in ventilation mode is same as it in cooling mode.
If set auto fan speed, the running speed is according to the temperature difference between room