JUNO-NET
STATUS
FIRE ALARM SYSTEM
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
PROC. FAULT
TRANS. FAULT
SOUND ALARMS
PAPER FEED
LAMP TEST
SYSTEM RESET
ALARM SILENCE
DISABLED
TEST
FAULT
FIRE
AUXILIARY
RELAYS
FIRE BRIGADE
TRANSMISSION
SELECTED
DETECTORS
ACTIVE
DELAYS
FIRE BRIGADE
ACKNOWLEDGED
ALARM DISPLAY
JUNO-NET
MANUFACTURED TO THE
REQUIREMENTS OF
EN54 Pt 2 & Pt 4 1999
FAULTS
CONTROLS
DISABLEMENTS
QUEUE REVIEW
1.1 DESCRIPTION OF THE FIRE CONTROL PANEL FASCIA
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
21
23
22
20
25
24
27
26
29
30
32
33
31
28
34
35
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
: If the LED is RED it indicates that there is a fire situation.
: If the LED is AMBER it indicates a fault situation. Additional information will be shown on the LCD display
and, if applicable, on the LEDs in the FAULTS section of the main panel (i.e. 7, 8, 9, 10).
: If the LED is AMBER it indicates that a detector is in PRE-ALARM.
: If the LED is AMBER it indicates that the panel is in a test mode.
: If the LED is AMBER it indicates that at least one disablement exists.
: If the LED is GREEN it means that the panel is in ACTIVE mode. If the LED is flashing GREEN then the
panel is in INSTALLATION mode.
: If the LED is AMBER it indicates that there is a problem with a loop sounder or conventional sounder
circuit. This could be an open or short circuit or a blown alarm fuse.
: If the LED is AMBER it indicates that there is a Primary Fault, a Battery Fault or that there is an Earth
Fault.
: If the LED is AMBER it indicates that there is 5 Volt fault or a program failure.
: If the LED is AMBER it indicates that there is an open or short circuit in the fire brigade
transmission circuit.
SUPPLY FAULT
PROCESSOR FAULT
TRANSMISSION FAULT
LCD DISPLAY
1
2
3
4
5
6
7
8
9
10
OPERATION
SECTION 1
2
OPERATION & MAINTENANCE MANUAL
REVISION 0.7a
16-04-2004

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Global JUNO-NET and is the answer not in the manual?

Global JUNO-NET Specifications

General IconGeneral
BrandGlobal
ModelJUNO-NET
CategoryFire Alarms
LanguageEnglish