0020092785_02 - 05/10 - Glow-worm
- 22 -
11.3.2 230V permanent supply + 230V system
controls
a
All cables connected to the appliance should be
permanently xed to the wall.
i
This appliance will not operate without a link or
system controls tted.
24
V
4
5
6
7
2
1
3
Key
1 230V permanent supply
2 System controls
3 Frost stat
4 Main board terminal block
FP=Froststat230V(switchable)
RT=Switchlive(230V)
= Mains earth
N = Mains neutral
L = Mains live
5 Junction box
6 Fuse
7 Double pole connector
Connect the mains supply and system heating controls e.g.
room thermostat as described.
11.4 External accessories
e
Under no circumstances must any mains voltage
be applied to any of the terminals on the 24v
connection plug.
230
V
X17
X18
RT 24V T° extBUS
BUS
24 V
3
4
2
1
Key
1 24V room thermostat connector
2 Ebus room thermostat connector or Ebus radio receiver/Smart
wiringcentre
3 Outdoor sensor connector
4 Overheatingsafetyconnectorforheatingoor
Fit external controls in accordance with the rules in force.
11.5 Testing the electrical connections
Carry out preliminary electrical system checks as below:
Resistance to earth (<1 Ohm)
Short circuit test (L-N)
Resistance to earth (L-E)
Polarity check
INSTALLATION