- 28 -
Code Parameter Unit Description
Factory
setting
Modiable
parameter
d.71
Maximum temperature setting for
heating outlet
°C Select a value between 50°C and 80°C. 75 yes
d.90 Detection of eBUS controller -
0 = Not detected
1 = Detected
- no
Press on button or under the symbol to access the
parameter to modify.
Press on button
or under the symbol to modify the
value of the parameter.
Repeat the process for each parameter modied.
Press for more than 3 seconds on the button
to exit
the conguration menu.
Code Parameter Unit Description
Factory
setting
Modiable
parameter
d.08 Current state of the 230V room thermostat -
230V room thermostat :
0 = open (no heating),
1 = closed (heating mode).
- no
d.09 Flow temperature set point from external eBus control °C External eBus set value. - no
d.10 Pump status -
0 = off
1 = on
- no
d.16 Current state of the 24V room thermostat °C
0 = open (no heating),
1 = closed (heating mode)
- no
d.17 Flow or Return temperature monitoring °C
Temperature regulation on ow (radiator) or return
(under-oor heating) temperature sensor.
0 yes
d.21 DHW status -
0 = DHW function disabled
1 = DHW activated
- no
d.22 DHW mode (eBus and direct connection to board) -
0 = off
1 = on
- no
d.23 Central heating mode -
0 = CH not available (summer mode)
1 = CH available (winter mode)
- no
d.25 DHW mode -
DHW loading enabled or disabled by Appliance
Interface or Ebus or external controls.
- no
d.33 Speed setpoint of fan rpm
Fan speed is displayed between 0 and 99.
Multiply the displayed value by 100.
- no
d.44 Digitalized ionisation voltage V Display the digitalized ionisation voltage - no
d.68 Unsuccessfull ignitions at rst attempt -
Display the number of unsuccessfull ignitions at rst
attempt.
- no
d.69 Unsuccessfull ignitions at second attempt -
Display the number of unsuccessfull ignitions at
second attempt.
- no
d.80 Operating hours in heating mode h
Display the number of operating hours in heating
mode. Multiply the displayed value by 100.
- no
d.81
Operating hours in domestic hot water mode (ebus
control only and direct thermostat connection to board
only)
h
Display the number of operating hours in domestic
hot water mode. Multiply the displayed value by 100.
- no
d.82 Number of burner starts in heating mode -
Display the number of burner starts in heating
mode. Multiply the displayed value by 100.
- no
d.83
Number of burner starts in DHW mode (ebus control
only)
-
Display the number of burner starts in DHW mode.
Multiply the displayed value by 100.
- no
d.93 Device Specic Number -
Select the product code of the appliance:
12sxi = 18
18sxi = 19
30sxi = 20
18
19
20
yes
d.96 Factory reset -
All parameters stored in EEPROM (main board +
appliance interface) are reset to factory settings if
this function is activated.
0 = deactivated
1 = activated
0 yes
13.2.2 After Sales Service settings
Press for more than 7 seconds on the button to
access the conguration menu. The screen displays "0".
Press on button
or under the symbol and enter the
After Sales Service password.
Press on
to validate. The screen displays the
parameter "00" and its value "XX”.
INSTALLATION