0020092785_02 - 05/10 - Glow-worm
- 47 -
19.4.1 Pump (head only)
Drain the boiler heating circuit as described in the
appropriate chapter "Draining".
Disconnect the electrical plug (26) from the main board.
Disconnect the electrical plug (25) from the pump head.
Remove the four cap head screws (27).
Carefully remove the pump head (28) together with cable.
Do not strain cable.
Reconnect wiring to new pump head and t cover.
Fit the new pump head by repeating the operations in
reverse.
19.4.2 Safety discharge valve
Drain the boiler heating circuit as described in the
appropriate chapter "Draining".
Undo the safety discharge valve union and remove from the
pipework (7).
Remove the securing clip (6) and withdraw the safety
discharge valve (8).
Fit new ‘O’ ring. Rell, vent and pressurise the boiler.
19.4.3 Automatic air vent
Drain the boiler heating circuit as described in the
appropriate chapter "Draining".
Remove the retaining clip (29).
Remove the automatic air vent (20).
Fit the new automatic air vent and ‘O’ ring ensuring the vent
cap is left loose.
Rell, vent and pressurise the boiler.
19.4.4 Lowwaterpressuresensor
Drain the boiler heating circuit as described in the
appropriate chapter "Draining".
Disconnect the electrical lead (15).
Remove the retaining clip (17), remove the low water
pressure sensor (16).
Fit the new low water pressure sensor.
Rell vent and pressurise the boiler.
19.4.5 Bypass
Drain the boiler heating circuit as described in the
appropriate chapter "Draining".
Remove the retaining clip (23) to remove the bypass screw (24).
After replacing the bypass, rell, vent and pressurise the
boiler.