Supplied By www.heating spares.co Tel. 0161 620 6677
12
5
5
A removable compartment door
can be placed a minimum of 15mm
051
5
5050
200
006
2 Boiler Location and Ventilation
2.1 Location
This boiler is not suitable for outdoor installation.
This boiler may be installed in any room, although particular
attention is drawn to the installation of a boiler in a room con-
taining a bath or shower where reference must be made to the
relevant requirements.
This boiler is suitable for installation in bathroom zones 2 and 3.
In GB this is the current I.E.E. WIRING REGULATIONS and
BUILDING REGULATIONS.
In IE reference should be made to the current edition of I.S.813
“Domestic Gas Installations” and the current ETCI rules.
2.2 Clearances
The boiler should be positioned so that at least the minimum
operational and servicing clearances are provided, see dia-
gram 2.1.
Additional clearances may be benefi cial around the boiler for
installation and servicing.
For fl ue installations where external access is not practicable,
consideration should be given for the space required to insert
the fl ue internally, which may necessitate clearance larger than
those specifi ed in diagram 2.1.
2.3 Timber Frame Buildings
If the boiler is to be installed in a timber frame building it should
be fi tted in accordance with the Institute of Gas Engineers doc-
ument IGE/UP/7/1998. If in doubt seek advice from local gas
undertaking or Glow-worm.
2.4 Room Ventilation
The boiler is room sealed so a permanent air vent is not re-
quired.
2.5 Cupboard or Compartment Ventilation
Due to the high effi ciency and hence low casing temperature of
this boiler, cupboard or compartment ventilation is not neces-
sary.
Leave existing air vents.
Diagram 2.1