9.17 Plume Management Kit
The Plume Management Kit: Part No. A2044100 (white) or
A2044000 (black) can be used to overcome many site issues.
The Plume Management Kit will fi t to the Top Horizontal Tel-
escopic, Rear Horizontal Telescopic and Standard Horizontal
Flue. This enables the fl ue products to exhaust further away
from the boiler, thereby reducing the impact of pluming. The
fl ue air inlet can be sited closer to doors, opening windows and
air bricks, see diagram 9.26.
The maximum length of the Plume Management Kit must NOT
exceed 6m with a horizontal concentric fl ue length of 2m max.
For each 90° bend or 2 x 45° bends the maximum length of the
Plume Management Kit must be reduced by 1m.
For more information contact Glow-worm, refer to page 2.
The Plume Management Kit is supplied with installation instruc-
tions.
Diagram 9.26
FLUE
OUTLET
FLUE
PRODUCTS
AIR INLET
PLUME
MANAGEMENT
KIT
25mm. MIN.
AIR BRICK
OPENING
WINDOW
OR DOOR
50mm.
MIN.
IMPORTANT: The flue outlet must
not be positioned within 300mm
from an opening, air brick or
opening windows.