15 Replacement of Parts
15.14 Condensate Trap
For access, refer to section 15.1.
Remove the drain outlet pipe from the base of the trap.
Remove the condensate drain securing screw and carefully
pull the trap forward, see diagram 13.12.
On the condensate trap there is a key symbol that should be
in line with the locked padlock symbol on the condense drain.
To remove the trap turn in the direction of the unlock symbol
and carefully pull down clear of the condense drain, see
diagram 13.12.
Remove any solids found in the condensate trap.
Flush water through the trap to remove any remaining solids.
Check for any debris in the outlet pipe of the condensate drain
and clean as necessary.
Reassemble and ret the condensate trap.
15.15 Heating Flow Thermistor
For access refer to section 15.1.
Remove the silencer front, fan/gas valve assembly and ue
hood for access. See relevant sections.
Refer to diagram 15.4.
Remove the electrical connections from the thermistor.
Remove the retaining clip from the ow pipe.
Remove the thermistor from the retaining clip.
Note that the polarity of the wiring to thermistors is
unimportant.
15.16 Heating Return Thermistor
For access, refer to section 15.1.
Refer to diagram 15.5.
Remove the electrical connections from the thermistor.
Remove the retaining clip from the return pipe.
Remove the thermistor from the retaining clip.
Note that the polarity of the wiring to thermistor is unimportant.
Diagram 15.4
13027
Diagram 15.5
13060

Other manuals for Glow-worm Flexicom 18sx

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Glow-worm Flexicom 18sx and is the answer not in the manual?

Glow-worm Flexicom 18sx Specifications

General IconGeneral
ModelFlexicom 18sx
CategoryBoiler
MountingWall Mounted
Output18 kW
Fuel TypeNatural Gas
ErP Heating Efficiency ClassA
Central Heating Max Pressure3 bar