SYSTEM OPERATION
91
TROUBLESHOOTING CHART ADV8, AMV8, ACV9, AMV9, GMV8, GCV9, GMV9
Fault
Description(s)
Symptoms of Abnormal
Operation
4
4 FLASHES
Associated
LED Code
2
Circulator blower runs
continuously. No furnace
operation.
Integrated control module
diagnostic LED is flashing
FOUR (4) flashes.
7
7 FLASHES
Normal furnace
operation.
Integrated control
module diagnostic LED
is flashing SEVEN (7)
flashes.
Furnace fails to operate.
Integrated control module
diagnostic LED is flashing
continuously.
C
CONTINUOUS
FLASHING
Primary limit
circuit is
open.
Polarity of
115 volt
power is
reversed.
Flame
sense
microamp
signal is
low.
Insufficient conditioned
air over the heat
exchanger. Blocked
filters, restrictive
ductwork, improper
circulator blower speed,
or failed circulator
blower.
Flame rollout.
Misaligned burners,
blocked flue and/or air
inlet pipe, or failed
induced draft blower.
Loose or improperly
connected wiring.
Possible Causes
Corrective Action
Cautions and Notes
Check filters and ductwork
for blockage. Clean filters or
remove obstruction.
Check circulator blower
speed and performance.
Correct speed or replace
blower if necessary.
Check burners for proper
alignment.
Check flue and air inlet
piping for blockage, proper
length, elbows, and
termination. Correct as
necessary.
Check induced draft blower
for proper performance.
Replace, if necessary.
Tighten or correct wiring
connection.
Turn power OFF
prior to repair.
See Product Data
Bulletin for
allowable rise range
and proper
circulator speed.
See “Vent/Flue
Pipe” section for
piping details.
Replace pressure
switch with proper
replacement part.
Polarity of 115 volt AC
power to furnace or
integrated control
module is reversed.
Poor unit ground.
Flame sensor is
coated/oxidized.
Flame sensor
incorrectly positioned
in burner flame.
Lazy burner flame due
to improper gas
pressure or combus-
tion air.
Review wiring diagram to
correct polarity.
Verify proper ground.
Correct if necessary.
Check and correct wiring.
Sand flame sensor is
coated/oxidized.
Inspect for proper sensor
alignment.
Check inlet air piping for
blockage, proper length,
elbows, and termination.
Compare current gas
pressure to rating plate info.
Adjust as needed.
Turn power OFF
prior to repair.
Turn power OFF
prior to repair.
Sand flame sensor
with emery clot.
See “Vent/Flue
Pipe” section for
piping details.
See rating plate
for proper gas
pressure.
Inspect
pressure
switch
hose.
Repair, if necessary.
Inspect flue and/or inlet air
piping for blockage, proper
length, elbows, and
termination.
Check
drain
system.
Correct
as
neces-
sary.
Correct pressure switch
setpoint or
contact motion.
Tighten
or
correct
wiring
connection.
9
9 FLASHES
Furnace not operating.
Integrated control module
diagnostic LED is
flashing EIGHT (8)
flashes.
• Furnace operating on
low stage gas with high
stage induced draft
blower
• High stage circulator
blower (temperature, of
conditioned air, lower
than typical).
Integrated control module
diagnostic LED is flashing
NINE (9) flashes.
8
8 FLASHES
High stage
pressure
switch
circuit
does not
close in
response
to high
stage
induced
draft
blower
operation.
Problem
with
igniter
circuit.
Improperly connected
igniter
Bad igniter
Poor unit ground
Pressure switch hose
blocked, pinched or
connected improperly.
Blocked flue and/or inlet
air pipe, blocked drain
system, or weak induced
draft blower.
Incorrect pressure switch
setpoint or malfunctioning
switch contacts.
Loose or improperly
connected wiring.
Check and correct wiring
from integrated control
module to igniter
Replace bad igniter
Check and correct unit
ground
wiring
Turn power OFF
prior to repair.
Replace igniter
with replacement
part.
Turn power OFF
prior to repair.
Replace
pressure switch
with proper
replacement
part.
Integrated control
module diagnostic LED is
flashing FIVE (5) times.
Induced draft blower
and circulator blower
run continuously. No
furnace operation.
Flame
sensed
with no call
for heat.
Correct short at flame
sensor or in flame sensor
wiring.
Check for lingering flame
Verify proper operation of
gas valve
Short to ground in flame
sense circuit.
Lingering burner flame.
Slow closing gas valve
Turn power OFF
prior to repair.
5
5 FLASHES
1
Integrated control module will automatically attempt to reset from lockout after one hour.
2
LED flash code will cease if power to control module is interrupted throught the disconnect or door switch.
4
Applies to ADV8, AMV8, GMV8 only.