SYSTEM OPERATION
90
TROUBLESHOOTING CHART ADV8, AMV8, ACV9, AMV9, GMV8, GCV9, GMV9
Furnace lockout
due to an
excessive
number of
ignition “retries”
(3 total)
1
.
Auxiliary limit
open
Locate and correct gas
interruption.
Replace or realign
igniter.
Check flame sense
signal. Sand sensor if
coated and/or oxidized.
Check flue piping for
blockage, proper length,
elbows, and termination.
Verify proper induced
draft blower perfor-
mance.
Check circulator blower
speed and performance.
Correct speed or
replace blower if
necessary.
Turn power OFF
prior to repair.
Igniter is fragile,
handle with care.
Sand flame sensor
with emery cloth.
See “Combustion
and Ventilation Air
Requirements” and
“Category I
Venting (Vertical
Venting)” section
for details.
See Product Data
Bulletin for
allowable rise
range and proper
circulator speed.
Furnace fails to operate.
Integrated control
module diagnostic LED
is flashing ONE (1)
flash.
1
1 FLASH
Failure to establish flame.
Cause may be no gas to
burners, bad igniter or
igniter alignment, improper
orifices, or coated/oxidized
or improperly connected
flame sensor.
Loss of flame after
establishment. Cause may
be interrupted gas supply,
lazy burner flames
(improper gas pressure or
restriction in flue or
improper induced draft
blower performance.
Insufficient conditioned air
over the heat exchanger.
Blocked filters, restrictive
ductwork, improper
circulator blower speed, or
failed circulator blower.
Low stage
pressure switch
circuit is closed.
Induced draft
blower is not
operating.
Replace induced draft
blower pressure
switch.
Repair short.
Turn power OFF
prior to repair.
Replace pressure
switch with proper
replacement part.
Furnace fails to operate.
Integrated control
module diagnostic LED
is flashing TWO (2)
flashes.
2
2 FLASHES
Induced draft blower
pressure switch contacts
sticking.
Shorts in pressure switch
circuit.
Inspect pressure
switch hose. Repair, if
necessary,
Inspect flue for
blockage, proper
length, elbows, and
termination.
Correct pressure
switch setpoint or
contact motion.
Tighten or correct
wiring connection.
Pressure switch hose
blocked, pinched or
connected improperly.
Blocked flue or weak
induced draft blower.
Incorrect pressure switch
setpoint or malfunctioning
switch contacts.
Loose or improperly
connected wiring.
Pressure
switch circuit
not closed.
Induced draft
blower is
operating.
Induced draft blower
runs continuously with
no further furnace
operation.
Integrated control
module diagnostic LED
is flashing THREE (3)
flashes.
3
3 FLASHES
Turn power OFF
prior to repair.
See “Combustion
and Ventilation Air
Requirements”
and “Category I
Venting (Vertical
Venting)” section
for details.
Replace pressure
switch with
proper replace-
ment part.
No 115 volt power
to furnace, or no 24
volt power to
integrated control
module.
Blown fuse or
circuit breaker.
Intergrated contol
module has an
internal fault
Manual disconnect switch
OFF, door switch open, or
24 volt wires improperly
connected or loose.
Blown fuse or circuit
breaker.
Intergrated contol module
has an internal fault
Assure 115 and 24 volt
power to furnace
integrated control
module.
Check integrated control
module fuse (3A).
Replace if necessary.
Check for possible
shorts in 115 and 24
volt circuits. Repair as
necessary.
Replace bad intergrated
control module.
Turn power OFF
prior to repair.
Replace integrated
control module
fuse with 3A
automotive fuse.
Read precautions
in “Electrostatic
Discharge” section
of manual.
Furnace fails to operate.
Integrated control
module diagnostic LED
provides no signal.
NONE
Fault
Description(s)
Possible Causes
Corrective Action Cautions and Notes
Symptoms of Abnormal
Operation
Associated
LED Code
2
LED is steady ON.
ON
CONTINUOUS
ON
Normal operation.
Normal operation.
• None.
Normal operation.
1
Integrated control module will automatically attempt to reset from lockout after one hour.
2
LED flash code will cease if power to control module is interrupted throught the disconnect or door switch.
4
Applies to ADV8, AMV8, GMV8 only.