SYSTEM OPERATION
89
2
LED flash code will cease if power to control module is interrupted throught the disconnect or door switch.
3
8 Flashes - Applies to AMS95, AMS9, ACS9 Models only (Silicon Nitride Models Only)
TROUBLESHOOTING CHART
AMS9, ACS9, DMS9, DCS9, GMS9,
GCS9, GKS9, AMS95, GMS95
5
5 FLASHES
6
6 FLASHES
8
8 FLASHES
Turn power OFF
prior to repair.
Replace primary/
auxiliary limit
switch with
proper replace-
ment part.
Replace blower
with correct
replacement part.
Turn power OFF
prior to repair.
Sand flame sensor
with emery clot.
See “Vent/Flue
Pipe” section for
piping details.
See rating plate for
proper gas
pressure.
Circulator blower runs
continuously. No
furnace operation.
Integrated control
module diagnostic LED
is flashing FOUR (4)
flashes.
Primary or
auxiliary limit
circuit is open.
Check primary/auxiliary limit.
Replace if necessary
Check filters and ductwork
for blockage. Clean filters or
remove obstruction.
Check circulator blower
speed and performance.
Correct speed or replace
blower if necessary.
Tighten or correct wiring
connection.
4
4 FLASHES
Insufficient conditioned air
over the heat exchanger.
Blocked filters, restrictive
ductwork, improper
circulator blower speed, or
failed circulator blower.
Faulty primary or auxiliary
limit switch.
Loose or improperly
connected wiring.
Fault
Description(s)
Possible Causes Corrective Action Cautions and Notes
Symptoms of Abnormal
Operation
Associated
LED Code
2
Furnace not operating.
Integrated control
module diagnostic LED
is flashing EIGHT (8)
flashes.
Problem with
igniter circuit.
Check and correct wiring
from integrated control
module to igniter.
Replace bad igniter.
Check and correct unit
ground wiring.
Turn power OFF
prior to repair.
Replace igniter
with proper
replacement part.
Improperly connected
igniter.
• Bad igniter.
Poor unit ground.
Normal furnace
operation.
Integrated control
module diagnostic LED
is flashing SEVEN (7)
flashes.
Flame sense
microamp signal
is low.
Sand flame sensor is
coated/oxidized.
Inspect for proper sensor
alignment.
Check inlet air piping for
blockage, proper length,
elbows, and termination.
Compare current gas
pressure to rating plate
info. Adjust as needed.
7
7 FLASHES
Flame sensor is coated/
oxidized.
Flame sensor incorrectly
positioned in burner flame.
Lazy burner flame due to
improper gas pressure or
combustion air.
Induced draft blower
and circulation blower
runs continuously. No
furnace operation.
Integrated control
module diagnostic LED
is flashing FIVE (5)
flashes.
Flame sensed
with no call
for heat.
Correct short at flame
sensor or in flame
sensor wiring.
Turn power OFF
prior to repair.
Short to ground in flame
sense circuit.
Circulator blower runs
continuously. No
furnace operation.
Integrated control
module diagnostic LED
is flashing SIX (6)
flashes.
Rollout limit
circuit is open.
Check burners for
proper alignment.
Check flue and air inlet
piping for blockage,
proper length, elbows,
and termination. Correct
as necessary.
Check induced draft
blower for proper
performance. Replace,
if necessary.
Tighten or correct wiring
connection.
Turn power OFF
prior to repair.
See “Vent/Flue
Pipe” section for
piping details.
Replace rollout
limit with correct
replacement part.
Replace induced
draft blower with
correct replace-
ment part.
Flame rollout.
Misaligned burners,
blocked flue and/or air
inlet pipe, or failed
induced draft blower.
Loose or improperly
connected wiring.
Faulty rollout limit.
Furnace fails to
operate.
Integrated control
module diagnostic LED
is flashing continu-
ously.
Polarity of 115
or 24 volt
power is
reversed.
Review wiring diagram to
correct polarity.
Reverse wires going to
24 volt side of trans-
former.
Verify proper ground.
Correct if necessary.
Turn power OFF
prior to repair.
C
CONTINUOUS/
RAPID FLASH
Polarity of 115 volt AC
power to furnace or
integrated control module is
reversed.
• Wires to 24 volt side of
transformer are reversed.
Poor unit ground.