SYSTEM OPERATION
88
1
Integrated control module will automatically attempt to reset from lockout after one hour.
2
LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.
TROUBLESHOOTING CHART
Cautions
and Notes
Turn power OFF
prior to repair.
Replace integrated
control module
fuse with 3A
automotive fuse.
Read precautions
in “Electrostatic
Discharge”
section of manual.
Turn power OFF
prior to repair.
Replace pressure
switch with proper
replacement.
lt Description(s)
• Normal Operation
LED is Steady On
ON
CONTINUOUS
No 115 volt power
to furnace, or no 24
volt power to
integrated control
module.
Blown fuse or
circuit breaker.
Integrated control
module has an
internal fault.
Manual disconnect
switch OFF, door switch
open, or 24 volt wires
improperly connected or
loose.
Blown fuse or circuit
breaker.
• Integrated control
module has internal
fault.
Assure 115 and 24 volt
power to furnace
integrated control module.
Check integrated control
module fuse (3A).
Replace if necessary.
Check for possible
shorts in 115 and 24 volt
circuits. Repair as
necessary.
Replace bad integrated
control module.
Furnace fails to operate.
Integrated control
module diagnostic LED
provides no signal.
NONE
Fault
Description(s)
Possible Causes
Corrective Action
Symptoms of Abnormal
Operation
Furnace lockout
due to an exces-
sive number of
ignition “retries” (3
total)
1
.
"Recycles" are
infinite.
Locate and correct gas
interruption.
Check front cover
pressure switch
operation (hose, wiring,
contact operation).
Correct if necessary.
Replace or realign
igniter.
Check flame sense
signal. Sand sensor if
coated and/or oxidized.
Check flue piping for
blockage, proper
length, elbows, and
termination.
Verify proper induced
draft blower perfor-
mance.
Turn power
OFF prior to
repair.
Igniter is
fragile, handle
with care.
Sand flame
sensor with
emery cloth.
See “Vent/
Flue Pipe”
section for
piping details.
Furnace fails to
operate.
Integrated control
module diagnostic LED
is flashing ONE (1) time.
1
Failure to establish flame.
Cause may be no gas to
burners, front cover
pressure switch stuck
open, bad igniter or igniter
alignment, improper
orifices, or coated/
oxidized or improperly
connected flame sensor.
Loss of flame after
establishment. Cause may
be interrupted gas supply,
lazy burner flames
(improper gas pressure or
restriction in flue and/or
combustion air piping),
front cover pressure
switch opening, or
improper induced draft
blower performance.
Pressure switch
circuit is closed.
Induced draft
blower is not
operating.
Replace induced draft
blower pressure switch.
Repair short.
Furnace fails to operate.
Integrated control
module diagnostic LED
is flashing TWO (2)
times.
2
Induced draft blower
pressure switch contacts
sticking.
Shorts in pressure switch
circuit.
Inspect pressure
switch hose. Repair, if
necessary,
Inspect flue and/or inlet
air piping for blockage,
proper length, elbows,
and termination. Check
drain system. Correct
as necessary.
Correct pressure
switch setpoint or
contact motion.
Tighten or correct
wiring connection.
Pressure switch hose
blocked, pinched or
connected improperly.
Blocked flue and/or inlet air
pipe, blocked drain
system, or weak induced
draft blower.
Incorrect pressure switch
setpoint or malfunctioning
switch contacts.
Loose or improperly
connected wiring.
Pressure switch
circuit not closed.
Induced draft
blower is
operating.
Induced draft blower
runs continuously with
no further furnace
operation.
Integrated control
module diagnostic LED
is flashing THREE (3)
times.
3
Turn power OFF
prior to repair.
Replace
pressure switch
with proper
replacement
part.
2 FLASHES
1 FLASH
3 FLASHES
Associated
LED Code
2
• Normal operation.
• Normal operation.
ON
• None.
AMS9, ACS9, DMS9, DCS9, GMS9,
GCS9, GKS9, AMS95, GMS95