SYSTEM OPERATION
87
TROUBLESHOOTING CHART
4
4 FLASHES
Circulator blower runs
continuously. No furnace
operation.
Integrated control module
diagnostic LED is flashing
FOUR (4) flashes.
6
6 FLASHES
7
7 FLASHES
Furnace fails to operate.
Integrated control module
diagnostic LED is flashing
SIX (6) flashes.
Normal furnace
operation.
Integrated control
module diagnostic LED
is flashing SEVEN (7)
flashes.
Rollout limit
open.
Flame sense
microamp signal is
low.
Insufficient conditioned
air over the heat
exchanger. Blocked
filters, restrictive
ductwork, improper
circulator blower speed,
or failed circulator
blower.
Check filters and
ductwork for blockage.
Clean filters or remove
obstruction.
Check circulator blower
speed and perfor-
mance. Correct speed
or replace blower if
necessary.
Turn power OFF
prior to repair.
See Product
Data Bulletin for
allowable rise
range and
proper circulator
speed.
Flame sensor is coated/
oxidized.
Flame sensor incor-
rectly positioned in
burner flame.
Lazy burner flame due
to improper gas
pressure or combustion
air.
Sand flame sensor is
coated/oxidized.
Inspect for proper
sensor alignment.
Check inlet air piping for
blockage, proper length,
elbows, and termination.
Compare current gas
pressure to rating plate
info. Adjust as needed.
Turn power OFF
prior to repair.
Clean flame
sensor with
steel wool.
See “Vent/Flue
Pipe” section for
piping details.
See rating plate
for proper gas
pressure.
See “Vent/Flue
Pipe” section for
piping details.
Replace induced
draft blower
with proper
replacement
part.
Primary limit
circuit is
open.
Integrated control module
diagnostic LED is flashing
continuously.
C
CONTINUOUS
FLASHING
Polarity of 115 volt
or 24 volt power
is reversed.
Polarity of 115 volt AC
power to furnace or
integrated control module
is reversed.
Wires to 24 volt side of
transformer are reversed.
• Poor unit ground.
Review wiring diagram
to correct polarity.
Reverse wires
connected to 24 volt
side of transformer.
Verify proper ground.
Correct if necessary.
Check and correct
wiring if necessary.
Turn power OFF
prior to repair.
8
8 FLASHES
3
• Check and correct
wiring from inte-
grated control module
to igniter.
Replace Bad igniter.
Check and correct
unit ground wiring.
Furnace not operating.
Integrated control
module diagnostic LED
is flashing EIGHT (8)
flashes.
• Problem with
igniter ciruit.
Improperly connected
igniter.
Bad igniter.
Poor unit ground.
• Turn power OFF
prior to repair.
Replace igniter
with proper
replacement
part.
• Normal operation.
LED is steady on
On Steady
Flame rollout.
Misaligned burners,
blocked flue and/or air
inlet pipe, or failed
induced draft blower.
Loose or improperly
connected wiring.
Check burners for
proper alignment.
Check flue and air inlet
piping for blockage,
proper length, elbows,
and termination.
Correct as necessary.
Check induced draft
blower for proper
performance. Replace,
if necessary.
Tighten or correct
wiring connection.
• Induced draft blower
and circulator blower
runs continuously. No
furnace operation.
• Integrated control
module diagnostic LED is
flashing FIVE (5) flashes.
5
5 FLASHES
Flame sensed
with no call
for heat.
Short to ground in flame
sense circuit.
Lingering burner flame.
Slow closing gas valve.
Correct short at flame
sensor or in flame
sensor wiring.
Check for lingering
flame.
Verify proper operation
of gas valve.
Turn power
OFF prior to
repair.
Fault
Description(s)
Symptoms of Abnormal
Operation
Associated
Possible Causes Corrective Action Cautions and Notes
• Normal operation. • None.
• Normal operation.
AMH8, AMS8, ADS8, DDS8, DMS8, DHS8,
GME8, GMH8, GMS8, GDH8, GDS8, GHS8
LED
Code
(2)(5)
2
LED Flash codes will cease if power to the control module is interrupted through the disconnect or door switch.
3
8 Flases - applies to AMS8/ADS8 Models only (Silicon Nitride Models Only)
5
Integrated circuit boards on new furnace models AMH, GMH, GCH, GMS, GDS, GHS, GKS hold last 5 faults for service reference.