WIRING DIAGRAMS
12
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
COOLING ONLY - 2 STAGE HEAT (T'STAT ENABLED OT)
NOTES:
1.) Y/Y2 ENABLES HI SPD FAN COOLING
2.) E/W1 ENABLES LO SPD FAN HEATING
W/W2 WITH OT CLOSED ENABLES HI SPD FAN HEATING
3.) OT1 PJ4 MUST BE CUT FOR THIS CONFIGURATION
OT2 PJ2 MUST BE CUT FOR THIS CONFIGURATION
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT
STAT OPENS ON HUMIDITY RISE
5.) DIP SWITCH #4 MUST BE IN THE "
ON" POSITION
OT2
PLEASE REFER
TO MANUAL
FOR PROPER
DIP SWITCH
CONFIGURATION.
(CFM)
HUM
ON
DIP
OFF
YCON
CONDENSER
R
E\W1
CONDENSING
UNIT
OUTDOOR
THERMOSTATS
HEATPUMP
W1
OT1
COM O
W2
W2 ED
W/W2 O OTC OT1
W1 W2
SWITCH
HEATER
CR
24 VAC
OT2 C RY1
W1
IF NEEDED
THERMOSTAT
ROOM
W2
C
RG
2nd STAGE HEATER
1st STAGE HEATER
HUMIDISTAT
(OPTIONAL)
SEE NOTE 4
Y1
HUM
HUMIDISTAT
Y/Y2G
Y
OUTDOOR
THERMOSTAT
1st STAGE ENABLED THRU ROOM T'STAT
2nd STAGE ENABLED THRU ROOM T'STAT AND CLOSED OT2
HEATPUMP - WITH 1 STG EMHT 1 STG AUX HEAT
NOTES:
1.) Y ENABLES HI SPD FAN COOLING
2.) E AND W2 ENABLE HI SPD FAN HEATING
3.) IF OT2 PJ2 JUMPER IS CUT E AND W2 ENABLE
LO SPD FAN HEATING
HUMIDISTAT
(OPTIONAL)
IF NEEDED
OT2OT1 Y1W/W2E\W1 C ROOTC
CONFIGURATION.
DIP SWITCH
FOR PROPER
TO MANUAL
PLEASE REFER
CONDENSER
YCONR
DIP
(CFM)
ON
OFF
OUTDOOR
W1
HUM
OT2
OT1
W2
HEATPUMP
COM O W2 ED
SWITCH
HEATER
W1 W2
24 VAC
C R
THERMOSTATS
HUMGY/Y2
Y1
HUMIDISTAT
SEE NOTE 4
1st STAGE HEATER
ROOM
THERMOSTAT
EC
RG
Y
HEATPUMP
RY
CO
W2
HEATPUMP
YCON
CONDENSER
R COM O W2 ED
W2
O
REMOVE
PRODUCTION
WIRE Y1 - O
4.)
CUT HUM PJ6 JUMPER IF USING HUMIDISTAT
STAT OPENS ON HUMIDITY RISE
5.) DIP SWITCH #4 MUST BE IN THE "
ON" POSITION