User Manual
V1.0-2022-11-15
Grid-Tied PV Inverter
MS Series
5-10kW

Other manuals for Goodwe GW10K-MS

Questions and Answers

  • N
    Nicole DicksonAug 19, 2025
    What to do if my Goodwe GW10K-MS shows 'PV Over Voltage'?
    • E
      Erica VillanuevaAug 19, 2025
      If your Goodwe Inverter displays a 'PV Over Voltage' error, follow these steps: First, turn off the DC switch, then disconnect both the AC and DC connectors. Check the PV string voltage to see if it exceeds the input voltage specified for your inverter. If it does, reconfigure the PV panel string. If the problem persists, contact your local service office for assistance.
  • P
    Patrick WalkerAug 21, 2025
    What to do if my Goodwe Inverter shows 'Utility Loss'?
    • L
      Lindsey LeachAug 21, 2025
      If your Goodwe Inverter shows a 'Utility Loss' message, take these steps: Begin by turning off the DC switch and disconnecting both the AC and DC connectors. Measure the voltage between the live line and neutral wire in the connector to ensure it meets grid-connected specifications. If it does not conform, check the distribution switch and grid for normal operation. If the voltage is within specification, reconnect the AC and DC connectors. Should the issue persist, contact your local service office.
  • M
    Matthew StewartAug 23, 2025
    What to do if my Goodwe GW10K-MS displays 'Isolation Failure'?
    • B
      buckleydebbieAug 23, 2025
      If your Goodwe Inverter is showing an 'Isolation Failure', here’s what to do: First, turn off the DC switch, then disconnect both the DC and AC connectors. Check the impedance between PV (+) & PV (-) to earth. If the impedance is less than 100K Ohms, inspect the insulation of the PV string wiring to the earth. If the impedance is greater than 100K Ohms, contact your local service office. Also, disconnect the AC connector and measure the impedance between the neutral wire and PE line; if it is greater than 10K Ohms, check the AC wiring.
  • Z
    Zachary WestAug 26, 2025
    What should I do if my Goodwe Inverter shows 'Ground I Failure'?
    • N
      Nicole RyanAug 26, 2025
      If your Goodwe Inverter is displaying a 'Ground I Failure', follow these steps: First, turn off the DC switch, then disconnect both the DC connector and AC connector. Check the insulation of the PV string wiring to the earth. Restart the DC switch. If the problem continues, please contact your local service office.
  • J
    Julia ContrerasAug 27, 2025
    What should I do if my Goodwe GW10K-MS Inverter shows 'Vac Failure'?
    • C
      Christopher SmithAug 28, 2025
      If your Goodwe Inverter is displaying a 'Vac Failure', follow these steps: First, turn off the DC switch, then disconnect the AC connector and DC connector. Measure the voltage between the live line and neutral wire in the connector, and check if it conforms to the grid-connected specification of the inverter. If it does not, check the grid wiring. If it conforms to the specification, reconnect the AC connector and restart the DC switch to allow the inverter to connect to the grid automatically. If the problem persists, contact your local service office.
  • B
    brittanymillerAug 30, 2025
    What to do if Goodwe GW10K-MS has no display?
    • M
      Mr. Samuel MclaughlinAug 30, 2025
      If your Goodwe Inverter has no display, follow these steps: Turn off the DC switch and disconnect the DC connector, then measure the voltage of the PV array. Plug in the DC connector and turn on the DC switch. If the PV array voltage is lower than 150V, check the configuration of the invert module. If the voltage is higher than 150V and the issue remains, please contact your local office.
  • G
    Gary GriffinSep 1, 2025
    How to resolve 'Over Temperature' error on Goodwe Inverter?
    • H
      Heather HamiltonSep 1, 2025
      To resolve an 'Over Temperature' error on your Goodwe Inverter: 1. Turn off the DC switch, then disconnect the AC and DC connectors. 2. Reduce the ambient temperature around the inverter. 3. Move the inverter to a cooler location. If the problem continues, contact your local service office for further assistance.
  • B
    brooksangelSep 3, 2025
    What to do if my Goodwe Inverter shows Utility Loss?
    • W
      wwhiteSep 3, 2025
      If your Goodwe Inverter displays a 'Utility Loss' error, first turn off the DC switch, then disconnect both the AC and DC connectors. Measure the voltage between the live line and neutral wire in the connector to ensure it meets the inverter's grid-connected specifications. If it doesn't, check the distribution switch and grid for normal operation. If it does meet specifications, reconnect the AC and DC connectors. If the problem persists, further assistance is needed.
  • M
    Mary BartlettSep 5, 2025
    What to do if Goodwe Inverter displays PV Overvoltage?
    • M
      Michele RoseSep 5, 2025
      If your Goodwe Inverter is showing a 'PV Overvoltage' error, begin by turning off the DC switch and disconnecting the AC and DC connectors. Check the PV string voltage to ensure it doesn't exceed the input voltage specified for your inverter. If it does, reconfigure the PV panel string. If the issue continues, seek further assistance.
  • T
    Teresa MannSep 7, 2025
    What to do if Goodwe GW10K-MS displays Vac Failure?
    • J
      Jason PerrySep 7, 2025
      If your Goodwe Inverter shows a 'Vac Failure', first turn off the DC switch and disconnect the AC and DC connectors. Measure the voltage between the live line and neutral wire in the connector to ensure it conforms to the inverter's grid-connected specification. If it does not, check the grid wiring. If it conforms, reconnect the AC connector and restart the DC switch, allowing the inverter to connect to the grid automatically. If the problem continues, further assistance is needed.

Summary

About This Manual

Applicable Model

Lists the inverter models covered by this manual.

Target Audience

Identifies the intended readers for this manual.

Symbol Definition

Explains the meaning of warning symbols used in the manual.

Updates

Notes that the document may be updated.

IMPORTANT SAFETY INSTRUCTIONS

General Safety

Provides essential safety precautions for operating the inverter.

DC Side

Details safety guidelines for the DC connections of the inverter.

AC Side

Outlines safety precautions for the AC connections and grid interface.

Inverter Installation

Covers safety warnings and requirements related to installing the inverter.

Personal Requirements

Specifies qualifications and training needed for personnel handling the equipment.

Product Introduction

Application Scenarios

Describes the intended use and function of the PV inverter.

Circuit Diagram

Presents a diagram illustrating the inverter's circuit connections.

Supported Grid Types

Lists the types of electrical grids the inverter is compatible with.

Appearance

Details the inverter's physical appearance, including parts identification, dimensions, indicators, and nameplate information.

Check and Storage

Check Before Receiving

Instructions for inspecting the product upon delivery.

Deliverables

Lists all items included in the product package.

Storage

Guidelines for storing the inverter safely when not in use.

Installation

Installation Requirements

Specifies the conditions and environment for inverter installation.

Inverter Installation

Details the step-by-step process for installing the inverter.

Electrical Connection

Safety Precaution

Outlines essential safety measures for electrical connections.

Connecting the PE Cable

Details the procedure for connecting the protective earth (PE) cable.

Connecting the PV Input Cable

Explains how to connect the DC input cables from the PV array.

Connecting the AC Output Cable

Guides on connecting the AC output cable to the grid.

Communication

Covers communication setup, including network introduction and cable connections.

Equipment Commissioning

Check Before Power ON

Checklist for verifying installation before powering up the inverter.

Power On

Step-by-step guide for powering on the inverter.

System Commissioning

Indicators and Buttons

Explains the function of inverter indicators and buttons.

Setting Inverter Parameters via LCD

Instructions for configuring inverter parameters using the LCD interface.

Upgrading the Firmware Via USB Flash Disk

Procedure for updating inverter firmware using a USB drive.

Setting Inverter Parameters via SolarGo App

Guide to configuring parameters using the SolarGo mobile application.

Monitoring via SEMS Portal

Information on using the SEMS Portal for system monitoring.

Maintenance

Power Off the Inverter

Steps to safely turn off the inverter before maintenance.

Removing the Inverter

Instructions for safely removing the inverter from its mounting.

Disposing of the Inverter

Guidelines for proper disposal of the inverter waste.

Troubleshooting

Methods for diagnosing and resolving common inverter issues.

Routine Maintenance

Procedures for regular upkeep and inspection of the inverter.

Technical Parameters

Goodwe GW10K-MS Specifications

General IconGeneral
Rated Output Power10000 W
Max. Input Voltage1100 V
Nominal AC Output Power10000 W
Max. AC Apparent Power11000 VA
Max. Output Current16 A
Nominal Output Voltage230 V
AC Output Frequency50/60 Hz
Number of MPPTs2
Number of DC Inputs2
Weight20 kg
Cooling MethodNatural cooling
Protection DegreeIP65
Max. DC Input Power13000 W
Max. AC Output Power10000 W
Nominal AC Voltage230 V
Operating Temperature Range-25°C to +60°C