User Manual
Grid-Tied PV Inverter
SDT G2 Series
V1.0-2022-01-17

Other manuals for Goodwe GW10K-SDT-20

Questions and Answers

  • V
    Vincent GreenSep 14, 2025
    What does ARC Fault mean on a Goodwe GW10K-SDT-20, and how do I fix it?
    • L
      Laura WoodSep 14, 2025
      An ARC Fault error on your Goodwe Inverter suggests that the PV string cables are arcing or are in poor contact. Check whether the PV terminals and cables are connected properly. Clear the error messages.
  • M
    Misty HarmonSep 23, 2025
    What does IFan Fail mean on my Goodwe GW10K-SDT-20?
    • Y
      yolanda86Sep 23, 2025
      An IFan Fail error on your Goodwe Inverter indicates a fault in the internal fan of the inverter. Restart the inverter and check whether the inverter can work normally.
  • M
    Mandy SimsSep 6, 2025
    How to resolve 'Ver. Error' on a Goodwe Inverter?
    • W
      wcontrerasSep 6, 2025
      If your Goodwe Inverter displays a 'Ver. Error', it indicates a wrong software version. Contact after-sales service to upgrade the software.
  • J
    James FarleyAug 27, 2025
    What does 'Vac Fail' mean on my Goodwe Inverter?
    • R
      Rebecca NobleAug 27, 2025
      If your Goodwe Inverter shows 'Vac Fail', it means the utility grid voltage is out of the allowed range. Make sure that the grid voltage is within the allowed range. Also, ensure that the phase sequence of the AC cables are connected correctly, and the neutral wire and PE cable are properly and firmly.
  • A
    Ashley MillerAug 27, 2025
    What causes 'Fac Fail' on a Goodwe Inverter?
    • S
      Steven CarrAug 27, 2025
      If your Goodwe Inverter shows 'Fac Fail', it indicates that the utility grid frequency is out of the allowed range. Check whether other electrical devices under the same grid connection point is working normally, and whether the main supply is normal. Ensure the grid frequency is within the allowed range and that the phase sequence of the AC cables are connected correctly, and the neutral wire and PE cable are properly and firmly. If the fault happens occasionally, it may be due to instantaneous utility grid frequency change and does not need to be handled.
  • T
    Tyler MayerAug 28, 2025
    Why is my Goodwe Inverter showing 'PV Over Voltage'?
    • S
      Sarah GarciaAug 28, 2025
      If your Goodwe Inverter displays 'PV Over Voltage', it means that too many PV modules are connected in series, causing the open-circuit voltage to exceed the operating voltage. Check whether the PV string input voltage is consistent with the value displayed on the LCD and meets the maximum input voltage requirements.
  • J
    Jason WilkersonAug 29, 2025
    What does 'ARC Fault' mean on my Goodwe GW10K-SDT-20 and how to fix it?
    • J
      Jennifer BuckAug 29, 2025
      If your Goodwe Inverter is showing an 'ARC Fault', it could be due to the PV string cables arcing or being in poor contact. Check whether the PV terminals and cables are connected properly. If the fault occurs frequently, contact after-sales service.
  • B
    bgarciaSep 17, 2025
    What causes a 'DC inject High' error on a Goodwe Inverter?
    • J
      jesusmillerSep 17, 2025
      A 'DC inject High' error on your Goodwe Inverter means that DC injection exceeds the allowed range. Check whether the software version is the latest one. Restart the inverter and check whether the inverter can work properly.
  • V
    Virginia MilesSep 15, 2025
    What does Ground I Fail mean on my Goodwe GW10K-SDT-20?
    • R
      Ruth HebertSep 16, 2025
      A Ground I Fail error on your Goodwe Inverter means that the input insulation impedance to the ground decreases when the inverter is operating. Check whether the working environment of the inverter meets the requirements. For example, the fault may occur due to high humidity on rainy days. Make sure that the components are properly grounded and the AC side is properly grounded.
  • T
    Toni WatsonSep 7, 2025
    What to do if my Goodwe Inverter shows a Utility Loss error?
    • R
      Rhonda ChurchSep 7, 2025
      If your Goodwe Inverter displays a Utility Loss error, it could be due to a utility grid power failure. Check if other electrical devices connected to the same grid connection point are working normally and if the main supply is normal. It could also be due to a disconnected AC circuit or AC breaker, so ensure that the upstream switches of the inverter are connected. Also, verify that the phase sequence of the AC cables are correctly connected, and the neutral wire and PE cable are properly and firmly connected.

Summary

Safety Precautions

General Safety Guidelines

Outlines essential safety rules for installation and operation.

DC Side Safety

Specific safety instructions for the DC electrical connections.

AC Side Safety

Safety measures related to AC electrical connections and grid requirements.

Installation

Installation Requirements

Specifies suitable locations and conditions for inverter installation.

Installing the Inverter

Step-by-step guide for securing the inverter on the mounting plate.

Electrical Connection

Electrical Connection Safety

Essential safety rules before making electrical connections.

Grounding (PE) Cable Connection

How to correctly connect the protective earth cable.

PV Input Cable Connection

Procedure for connecting the solar panel DC input cables.

AC Output Cable Connection

Steps for connecting the inverter to the AC grid.

Equipment Commissioning

Pre-Power On Checks

Checklist before switching the inverter on for the first time.

Power On Procedure

Sequence of operations to safely power up the inverter.

System Commissioning

Maintenance

Goodwe GW10K-SDT-20 Specifications

General IconGeneral
ModelGW10K-SDT-20
Number of MPPT2
Nominal Grid Frequency50/60Hz
THDi<3%
DC SwitchYes
Protection ClassI
Protection LevelIP65
Rated Power10kW
Maximum Power Output11kW
Nominal AC Output Power10kW
Max. AC Apparent Power11kVA
Nominal AC Voltage220/230V
AC Voltage Range180-280V
Power Factor0.8 leading ~ 0.8 lagging
Operating Temperature Range-25°C to 60°C
CommunicationWiFi/GPRS/RS485