Goodwe GW10K-ET - User Manual

Goodwe GW10K-ET
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
User Manual
V1.1-2022-12-20
Hybrid Inverter
ET Series / ET Plus Series
5.0-10.0kW
AC-Coupled Inverter
BT Series
5.0-10.0kW

Other manuals for Goodwe GW10K-ET

Questions and Answers

  • R
    Rebecca GuzmanSep 15, 2025
    What to do if Goodwe GW10K-ET Inverter shows PV Continuous Hardware Overcurrent?
    • N
      Nicholas GrantSep 15, 2025
      To address a 'PV Continuous Hardware Overcurrent' error on your Goodwe Inverter, disconnect the AC output switch and DC input switch, then reconnect them after 5 minutes. If the problem persists, contact the dealer or after-sales service.
  • C
    Carlos RamirezAug 25, 2025
    What to do if Smart Meter & CT connections are not working on Goodwe Measuring Instruments?
    • K
      Kenneth FergusonAug 25, 2025
      To resolve issues with Smart Meter & CT connections in your Goodwe Measuring Instruments, ensure that the Smart Meter and CT are properly connected between the house loads and the grid. Also, make sure to follow the Smart Meter direction sign on the CT.
  • A
    Andrew DavisAug 26, 2025
    How to troubleshoot on-grid and backup connections in Goodwe Measuring Instruments?
    • R
      rebeccacurtisAug 26, 2025
      To resolve on-grid and backup connection problems with Goodwe Measuring Instruments, verify that the on-grid is connected to the power grid and the backup is connected to the loads. Also, check that the polarities (e.g. L1/L2/L3/N) are correctly aligned.
  • P
    Paul MillerAug 26, 2025
    Why is my Goodwe Inverter showing a utility loss?
    • C
      Craig DuarteAug 27, 2025
      If your Goodwe Inverter is showing a utility loss, it could be due to a failure in the utility grid power or because the AC cable is disconnected, or the AC circuit breaker is off. Once the grid power supply is restored, the alarm should automatically clear. Ensure the AC cable is securely connected and the AC circuit breaker is turned on.
  • D
    Dr. Kirk HortonSep 16, 2025
    What to do if Goodwe Inverter shows PV Continuous Software Overcurrent?
    • J
      Jodi HarrisSep 16, 2025
      To address a 'PV Continuous Software Overcurrent' error on your Goodwe Inverter, disconnect the AC output switch and DC input switch, then reconnect them after 5 minutes. If the problem persists, contact the dealer or after-sales service.
  • T
    Tanya PerrySep 23, 2025
    How to check battery connections on Goodwe Measuring Instruments?
    • C
      Cynthia HarrisSep 23, 2025
      To solve battery connection issues in Goodwe Measuring Instruments, confirm that the connections between the ET and the battery are properly established.
  • P
    Pamela RileySep 8, 2025
    Why is my Goodwe GW10K-ET showing a Cavity Overtemperature error?
    • J
      Jeremy MoralesSep 8, 2025
      A 'Cavity Overtemperature' error on your Goodwe Inverter can be due to several reasons: 1. The inverter is installed in a location with poor ventilation. 2. The ambient temperature exceeds 60°C. 3. There is a fault with the internal fan of the inverter. To address this, first, check the ventilation and ambient temperature at the installation point. If ventilation is poor or the temperature is too high, improve ventilation and heat dissipation. If both are normal, contact the dealer or after-sales service.
  • G
    gregory25Sep 9, 2025
    What does Anti-islanding mean on Goodwe GW10K-ET Inverter?
    • J
      Jose WilliamsSep 9, 2025
      An 'Anti-islanding' error on your Goodwe Inverter indicates that the utility grid is disconnected, but the grid voltage is maintained due to the loads, according to safety regulations. Check whether the utility grid is disconnected and contact the dealer or after-sales service.
  • M
    Maria RobinsonSep 2, 2025
    How do I fix a PV Input Overvoltage error on my Goodwe GW10K-ET?
    • C
      craig39Sep 3, 2025
      A 'PV Input Overvoltage' error on your Goodwe Inverter means that too many PV panels are connected in series in the PV string. Check the serial connection of the PV array, ensuring that the open circuit voltage of the PV string does not exceed the inverter's maximum operating voltage.
  • M
    Michael KellerAug 31, 2025
    What causes an Abnormal GFCI 30mA error on a Goodwe GW10K-ET Inverter?
    • N
      Nicholas CochranSep 1, 2025
      An 'Abnormal GFCI 30mA' error on your Goodwe Inverter indicates that the input insulation impedance has become low during operation. If this occurs occasionally, it might be due to a cable issue, and the inverter should recover automatically once the problem is resolved. However, if the problem occurs frequently or persists, check whether the impedance between the PV string and PE is too low.

Summary

Safety Precautions

General Safety Guidelines

Provides essential safety instructions for operating and installing the inverter.

Inverter Safety

Details specific safety measures and warnings related to the inverter unit.

Battery Safety

Outlines crucial safety guidelines for battery handling and connection.

Installation

Installation Requirements

Details environmental, placement, and operational criteria for installation.

Inverter Mounting Procedure

Step-by-step instructions for physically mounting the inverter to its location.

Electrical Connection

Electrical Connection Safety

Critical safety warnings and precautions before making electrical connections.

Equipment Commissioning

Power On Procedure

Step-by-step guide for safely powering on the inverter.

System Commissioning

Maintenance

Powering Off the Inverter

Procedures for safely shutting down the inverter before maintenance.

Troubleshooting Guide

Lists common faults, their causes, and recommended solutions.

Technical Parameters

Goodwe GW10K-ET Specifications

General IconGeneral
ModelGW10K-ET
Max. DC Input Voltage1000 V
Number of MPPTs2
Rated AC Output Power10000 W
Max. AC Output Power11000 VA
Frequency50 Hz / 60 Hz
Efficiency98.3%
Dimensions516 x 415 x 180 mm
Weight25 kg
Max. DC Input Power13000 W
Start Voltage180 V
MPPT Voltage Range200V - 1000V
Number of MPP Trackers2
Max. Short Circuit Current per MPPT15 A
Nominal AC Output Power10000 W
Max. AC Apparent Power11000 VA
Nominal AC Voltage230 V / 400 V
Nominal Grid Frequency50 Hz / 60 Hz
THDi<3%
DC SwitchYes
Protection ClassIP65
Operating Temperature Range-25°C to +60°C
Cooling MethodNatural Convection
Rated Output Power10000 W
Grid Frequency50 Hz / 60 Hz
Max. Efficiency98.3%
Noise Level<30 dB
Protection DegreeIP65
TypeThree Phase
AC Voltage Range180V - 280V
Power Factor0.8 leading - 0.8 lagging
Rated Grid Voltage230 V