4
02 Safety Precaution User Manual V1.1-2022-12-20
DANGER
Do not apply mechanical load to the terminals, otherwise the terminals can be damaged.
All labels and warning marks should be visible after the installation. Do not cover, scrawl,
or damage any label on the equipment.
Warning labels on the inverter are as follows:
HIGH VOLTAGE HAZARD
Disconnect all incoming
power and turn o the
product before working on it.
Delayed discharge. Wait
5 minutes after power o
until the components are
completely discharged.
Read through the user
manual before any
operations.
Potential risks exist. Wear
proper Personnel Protective
Equipment before any
operations.
High-temperature hazard. Do
not touch the product under
operation to avoid being
burnt.
Grounding point.
CE Mark Do not dispose of the
inverter as household waste.
Discard the product in
compliance with local laws
and regulations, or send it
back to the manufacturer.
2.3 Inverter Safety
WARNING
The voltage and frequency at the connection point should meet the inverter grid
connection requirements.
Additional protective devices like circuit breakers or fuses are recommended on the AC
side. Specication of the protective device should be at least 1.25 times the maximum AC
current.
PE cable of the inverter must be connected rmly. The resistance between the neutral wire
and the earth cable is less than 10Ω.
You are recommended to use copper cables as AC output cables. Contact the manufacturer
if you want to use other cables.
When single overload protection occurs, the inverter can restart automatically; however,
the restarting time will be extended if it happens several times. For a faster restarting, try it
via app.
Do not enable the BACK-UP function if the PV system is not congured with batteries.
Otherwise, the manufacturer shall not be liable for related risks.

Other manuals for Goodwe GW10K-ET

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Goodwe GW10K-ET and is the answer not in the manual?

Goodwe GW10K-ET Specifications

General IconGeneral
ModelGW10K-ET
Max. DC Input Voltage1000 V
Number of MPPTs2
Rated AC Output Power10000 W
Max. AC Output Power11000 VA
Frequency50 Hz / 60 Hz
Efficiency98.3%
Dimensions516 x 415 x 180 mm
Weight25 kg
Max. DC Input Power13000 W
Start Voltage180 V
MPPT Voltage Range200V - 1000V
Number of MPP Trackers2
Max. Short Circuit Current per MPPT15 A
Nominal AC Output Power10000 W
Max. AC Apparent Power11000 VA
Nominal AC Voltage230 V / 400 V
Nominal Grid Frequency50 Hz / 60 Hz
THDi<3%
DC SwitchYes
Protection ClassIP65
Operating Temperature Range-25°C to +60°C
Cooling MethodNatural Convection
Rated Output Power10000 W
Grid Frequency50 Hz / 60 Hz
Max. Efficiency98.3%
Noise Level<30 dB
Protection DegreeIP65
TypeThree Phase
AC Voltage Range180V - 280V
Power Factor0.8 leading - 0.8 lagging
Rated Grid Voltage230 V