Goodwe GW10KN-ET - User Manual

Goodwe GW10KN-ET
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
User Manual
V1.1-2022-12-20
Hybrid Inverter
ET Series / ET Plus Series
5.0-10.0kW
AC-Coupled Inverter
BT Series
5.0-10.0kW

Other manuals for Goodwe GW10KN-ET

Questions and Answers

  • S
    Sharon HernandezSep 18, 2025
    What to do if Goodwe GW10KN-ET shows PV Continuous Software Overcurrent?
    • D
      Destiny ReillySep 22, 2025
      To address a 'PV Continuous Software Overcurrent' error on your Goodwe Inverter, disconnect the AC output switch and DC input switch, then reconnect them after 5 minutes. If the problem persists, contact the dealer or after-sales service.
  • J
    Jessica MaxwellAug 25, 2025
    How to troubleshoot on-grid and backup connections in Goodwe Measuring Instruments?
    • B
      brucegreerAug 25, 2025
      To resolve on-grid and backup connection problems with Goodwe Measuring Instruments, verify that the on-grid is connected to the power grid and the backup is connected to the loads. Also, check that the polarities (e.g. L1/L2/L3/N) are correctly aligned.
  • L
    Laurie RichardsAug 25, 2025
    Why is my Goodwe GW10KN-ET Inverter showing a utility loss?
    • J
      Jonathan FranklinAug 26, 2025
      If your Goodwe Inverter is showing a utility loss, it could be due to a failure in the utility grid power or because the AC cable is disconnected, or the AC circuit breaker is off. Once the grid power supply is restored, the alarm should automatically clear. Ensure the AC cable is securely connected and the AC circuit breaker is turned on.
  • T
    Timothy LongAug 27, 2025
    What to do if my Goodwe Inverter shows 'Low Insulation Res.'?
    • J
      jessicadixonAug 27, 2025
      A 'Low Insulation Res.' error on your Goodwe Inverter typically means one of two things: either the PV string is short-circuited to PE, or the PV system is in a moist environment with poorly insulated cables. To resolve this: 1. Check if the resistance of the PV string to PE exceeds 50k?. If not, identify and fix the short circuit. 2. Verify that the PE cable is correctly connected. 3. If the resistance drops on rainy days, reset the ISO via the SolarGo app.
  • C
    Cody PerezSep 23, 2025
    How to check PV input connection on Goodwe Measuring Instruments?
    • A
      agraySep 23, 2025
      To fix PV input connection problems with your Goodwe Measuring Instruments, confirm that the connections between the ET and PV panels are correctly established.
  • M
    Mr. Daniel SnyderSep 23, 2025
    How to check battery connections on Goodwe Measuring Instruments?
    • L
      Laura WattsSep 23, 2025
      To solve battery connection issues in Goodwe Measuring Instruments, confirm that the connections between the ET and the battery are properly established.
  • C
    Crystal JohnsonSep 10, 2025
    What does Anti-islanding mean on Goodwe Inverter?
    • B
      barbarabarrettSep 12, 2025
      An 'Anti-islanding' error on your Goodwe Inverter indicates that the utility grid is disconnected, but the grid voltage is maintained due to the loads, according to safety regulations. Check whether the utility grid is disconnected and contact the dealer or after-sales service.
  • P
    psmithSep 12, 2025
    What causes Anti Reverse power Failure on Goodwe Inverter?
    • C
      Catherine HarveySep 12, 2025
      An 'Anti Reverse power Failure' on your Goodwe Inverter is due to abnormal fluctuation of load. If the exception is caused by an external fault, the inverter will recover automatically after solving the problem. If the problem occurs frequently and the PV station cannot work properly, contact the dealer or the after-sales service.
  • G
    gkelleySep 3, 2025
    Why am I getting an Abnormal Ground error on my Goodwe GW10KN-ET?
    • D
      Donna BurkeSep 4, 2025
      An 'Abnormal Ground' error on your Goodwe Inverter can be caused by two main issues: either the PE cable of the inverter is not properly connected, or the L and N cables are connected reversely when the output of the PV string is grounded. To resolve this, first, check whether the PE cable of the inverter is connected properly. Second, check whether the L and N cables are connected reversely if the output of the PV string is grounded.
  • M
    Michael FoxSep 1, 2025
    What does Grid Rapid Overvoltage mean on Goodwe GW10KN-ET?
    • M
      Marie HerreraSep 1, 2025
      A 'Grid Rapid Overvoltage' error on your Goodwe Inverter indicates an abnormal or ultra-high grid voltage. If the problem occurs occasionally, it may be a temporary issue with the utility grid, and the inverter should recover automatically. If the problem occurs frequently, check whether the grid voltage is within the allowed range. If it exceeds the permissible range, contact the local power company. If the grid voltage is within the permissible range, you may need to modify the grid overvoltage rapid protection threshold after obtaining consent from the local power company.

Summary

Safety Precautions

General Safety Guidelines

Outlines essential safety precautions for installation, operation, and general handling of the inverter.

Inverter and Battery Safety

Covers critical safety instructions for the inverter unit and connected battery systems.

Installation and Handling

Installation Environment Requirements

Details the environmental conditions and site requirements for installing the inverter.

Mounting and Installation Steps

Guides through the process of moving and physically mounting the inverter.

Electrical Connections

Connection Safety Precautions

Emphasizes safety precautions to be followed during all electrical connection procedures.

DC, AC, and PE Cable Connections

Guides on connecting DC input, AC output, and PE grounding cables.

System Commissioning

Power On Procedure

Details the step-by-step sequence for safely powering on the inverter and its components.

Maintenance and Troubleshooting

Powering Off and Removing the Inverter

Provides procedures for safely powering off and removing the inverter.

Troubleshooting Common Issues

Offers solutions for common faults and issues encountered with the inverter.

Technical Specifications

Goodwe GW10KN-ET Specifications

General IconGeneral
ModelGW10KN-ET
Rated Output Power10000W
Start Voltage200 V
Number of MPPT2
Max. Input Current per MPPT13 A
Max. AC Apparent Power11000VA
THDi< 3%
Rated Grid Frequency50/60 Hz
Euro Efficiency97.5%
DC SwitchYes
Protection DegreeIP65
Max. DC Input Power13000 W
AC Voltage Range180-280 V
Power Factor0.8 leading ... 0.8 lagging
Operating Temperature Range-25 °C to +60 °C
CommunicationRS485
Cooling MethodNatural cooling