765041982 Rev. 000 25
Cleaning the condenser filter / resetting the FILTER alarm
After 600 compressor running hours the filter must be
cleaned.
After cleaning the air filter, the controller must be reset to
remove the alarms.
It can only be reset by using a certain key combination.
Key combination: .
After 600 compressor running hours "FILTER" lights
yellow.
After 625 compressor running hours "FILTER" begins to
flash and the service symbol lights white.
After 650 compressor running hours "FILTER" flashes red
and the service symbol lights lyser yellow.
After 675 compressor running hours the alarm symbol
lights and an acoustic alarm sounds.
Push 3 x and 3 x :
FILTER symbol lights green for
approx. 1 minute, and is then turned
off.
